52
08/13424999756
Connection facilities
•
24 V DC drives with separate cutoff (load interruption, limit switch)
•
total power consumption of all connected drives max. 4 A or 8 A depending on type of control panel
•
10 SHEV control points RBH/3A... (line terminal via attached terminal resistor)
•
10 automatic detectors in 2-conductor technology, optical smoke detectors and/or heat differential detectors and/or
maximum heat detectors (line terminal with active end module or terminal resistor) factory-fitted via attached termi-
nal resistor
•
10 external ventilation switches OPEN/STOP/CLOSE (e.g.: type LTA 25) per ventilation group, max. two ventilation
groups
•
Power supply 24 V DC - 100 mA for one wind/rain detector WRS 24V or one rain detector RS
•
one connection each for potential-free signal of SHEV triggered and malfunction plus transmission of wind/rain sig-
nal; contact load 30 V / max. 2 A
•
Maximal 8 control pane Slave are cascadable
* The functions are dependent on the firmware used by the control panel and the scope of the PC configuration software.
Compact control panel 4A, 4A/M und 8A, 8A/M
230 V AC
M1
=
STOP
Lüftung/VENT
Rauchabzug
Smoke heat extraction
STOP
Lüftung/VENT
!
10 1
1
1 2
3
4
5
6
7
8
9
12
ON
OK
:
Reset
12V
=
M2
+ -
N L
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39
M1
=
=
M2
12V
!
2 1
6
2 1
10
fuse
rechargeable battery
fuse
rechargeable battery
connection
" SHEV-close"
switch,reset
LED indicators
DIP-switch
PC interface
Motor 2
Motor 1
fuse
interface 4 - 20 mA
potential-free input