Troubleshooting
Malfunction - beep code - chart
The pulse sequence gives information regarding the source of the malfunction. The continuous acoustical signal rings
out only by SHE man. call point with buzzer and if the door contact switch is pressed.
Note:
The yellow LED
- malfunction, the red LED
- SHE activation and the green LED
OK
-
operating OK lits up permanently during the memory checks.
Malfunction master-slave function
7 x short flash:
Collective Display upstream control panel for the malfunctioning of a slave control panel. The defective slave unit flash
the fault according to beep code table. Has no slave headquarters resulted in an error, then the
communication line between two panels not connected or the dip switch 8 of the last slave panel is set incorrectly
(must be OFF).
1 long and 6 x short flash:
The UEB2 module is connected incorrectly. Error indication only at the slave center that caused the error.
Maintenance (steady flash)
The green LED
OK
- Operation OK - flashes steadily: Reset or putting of maintenance timer by configuration-software
of compact control panel 4A and 8A. More information please see technical information of PC software Service Port of
compact control panel 4A and 8A.
Wind-/or rain signal (steady flash)
Indicator lamp in the ventilation switch LTA 25
Open display
(to last signal)
__________________________
Indicator lamp in the ventilation switch LTA25. The indicator lamp indicates at ventilation function stop or Open.
Maintenance
Compact control panel 4A, 4A/M und 8A, 8A/M
all OK
mains failurel
battery failure
malfunction SHE manual call point
malfunction autom. detector
malfunction motor monitoring circuit
0 x
1 x
2 x
5 x
4 x
3 x
6 x
8 x
7 x
memory error
malfunction master-slave function
Incorrect connection UEB2 module