Instruction for use

1

2

3

4

5

6

7

1

2

3

4

5

6

7

230VAC

power supply

drive group

2x group

3x group
optional

alarm

display

panel

detector

contacts

control

contact

of

external

system

2 x group

vent

button

2 x lines

smoke or

thermal

detector

2 x lines

smoke vent

button

rain

detector

2 x lines

Smoke Vent Control Panel RZN 4304/08-M

Installation

This system is designed to protect lives and safeguard valuable property!

Annual function check by manufacturer or duly authorized specialist.

Wiring, installation and functional testing only by qualified electrician.

The green pilot lights on the vent buttons must be lit up at all times,

otherwise refer to "Troubleshooting".

Rectify power failure without delay. Emergency power supplied for 72 hours.

Guarantee

You will get 

2 years 

guarantee for all D+H products from date of verified handing over of the

system up to maximal 3 years after date of delivery, when mounting and starting has been
carried out by a D+H authorized  

distributor

.

D+H guarantee is expired, with connection of D+H components with external systems or
with mixing of  D+H products with parts of other manufacturers.

Summary of Contents for RZN 4304

Page 1: ...uable property Annual function check by manufacturer or duly authorized specialist Wiring installation and functional testing only by qualified electrician The green pilot lights on the vent buttons m...

Page 2: ...2 LED DRIVES GROUP 2 fuse DIP switchblock S2 DIP switchblock S1 ALARM LINIE 2 LED FAULT LINIE 2 LED FAULT LINIE 1 LED ALARM LINIE 1 LED ALARM RESET Line ON OFF Reset detectors ALARM RESET Line ON OFF...

Page 3: ...em 400m Min clearance from walls beams etc 50cm Do not mount in airflow from ventilation systems or domelights Fire extinguishing systems must not adversely affect the detectors In case of sprinkler s...

Page 4: ...4 12 RZN 430x M Rev 1 6 Standard Connection with RT 42 11...

Page 5: ...nt button RT 42 On smoke vent buttons with a lower PCB serial no than DH4642 see rear of PCB Line connection to next smoke vent button from terminal 2 Terminal 7 is without significance Fire detectors...

Page 6: ...imate LT 43 thermal detector THE4 ye bk bk closed open signal optional open monitored Mot a Mot b L L P P bl bu br bn control alarm closed general malfunction Smoke vent button RT 43 H RT 43 N 10kW al...

Page 7: ...button each first to penultimate smoke vent button each Shunt connection by customer S general malfunction E1 Parallel Connection of Smoke Vent Buttons RT 43 H N Terminal resistors for line monitoring...

Page 8: ...ctor using the smoke heat vent button DIP switches 3 must be OFF DIP switch 4 ON The vent closes completely after the vent button has been pressed once If DIP switch 4 is OFF the vents will only close...

Page 9: ...nt button First all open the system then close it again Activate fire detectors with D H smoke detector test unit or cigarette smoke Re sponse time lag approx 20 sec The red LED must light up and the...

Page 10: ...fuse and connections Check fuse connections cables terminal resistors on drives Check terminal resistor or module between terminals 5 and 7 Check terminal resistor or module between terminals 5 and 6...

Page 11: ...which operate by thermal ascending force and by automatic fire recognition devices thermal detector smoke detector and they release either self acting or manual by smoke detectors at an early stage of...

Page 12: ...up end Example 1 1 Lane Simple wiring however unfavourable for voltage drop All drives on one line Example 2 2 lanes Control panel in the centre one side wired as branch the other one as terminal line...