Compact control panel 4A, 4A/M und 8A, 8A/M
Start up procedure and trial run
Note:
The specifications for start up procedure apply to the standard functions.
All DIP-Switches are OFF.
Note:
Before commissioning, check whether the batteries are fixed suitably firmly by the velcro tapes
or bracket depending. Operation without securely fastened batteries is not permitted!
Without mains voltage and without battery
Check all parts mechanically and electrically for fully tightened screw connections and damage, the terminals: plug in
connectors for motors and control elements as well as, if available, automatic detectors and wind/rain detectors.
Do not plug in the battery fuse!
With mains voltage, with battery
Plug on the battery connector, the battery connector is polarized. If it is removed, make sure the polarity is correct.
Attention:
Polarity reversal leads to destruction.
Visual display on the control board
Max. 100 secs. after connecting the battery, check:
green LED
OK
- Operation OK - lit up,
red LED
- SHE activation - not lit up
yellow LED
- SHE activation - not lit up
Troubleshooting
•
green LED
OK
not lit up: Mains and/or battery and connection not OK.
•
red LED
lit up: Press SHE-Reset switch in the control panel.
•
Yellow LED
is flashing:
check corresponding fuses (see also beep code chart page 72).
cable breakage, check cable connections.
check if end module is missing in last smoke detector.
* not included in delivery.
Vent switches
Press vent switch Open briefly, the drives open the windows completely up to end position.
The display “ventilation Open” lights up. During running: observe the windows exactly.
Attention: Make sure the drives can move freely at all times without obstruction. Pay attention to potential collisi-
on, tension and crushing during this movement, too. Check the connection cables of the drives: they must not be strained
by tension or crushing.
Press vent switch CLOSED briefly, the drives close the window. The display “Ventilation OPEN” goes out. Press STOP
during running, STOP = press both OPEN and CLOSED switches at the same time, the drives stop.
The display “Ventilation OPEN” lights up.
Press vent switch CLOSED briefly once again, the drives run to CLOSED. The display “Ventilation OPEN” goes out. The
drives close the window completely up to end position. The display “Ventilation OPEN” goes out.
Attention:
Pay attention to potential collision, tension and crushing during this movement, too