Function of DIP-Switches
The following switch combinations provide special functions
:
1. DIP-Switches 2 + 3 = ON (combinations with DIP-Switches 4, 5, 7-12 also possible).
Function:
•
the ventilation push button inputs have no function
•
no motor timing device (in SHE for 30 mins., VdS function)
•
no cut-out of the motor voltage after 3 minutes, for SHE CLOSE
•
with return of the mains voltage the motor outputs are: automatically switched in CLOSED direction
•
24 V DC output at the terminals 21(+) and 22 (-), in the event of failure of the mains voltage the voltage continues
•
to be applied for 3 mins (assuming that batteries are operationally ready)
•
relay contact for wind/rain signal with modified assignment and switching criterion
•
the relay switches (de-energises) in the event of a composite fault and/or wind/rain signal
•
assignment: terminal 33 = arm, terminal 34 = closer, terminal 35 = opener
2. DIP-Switches 2 + 3 + 6 = ON
(combinations with DIP-Switches 4, 5, 7-12 also possible).
Identical with the function DIP 2 + 3 = ON, but with the following modifications:
• the special functions do not affect motor output 1 or the ventilation push button input for motor group 1.
3. DIP-Switches 4 + 8 = ON
(combinations with DIP-Switches 1-3, 5-7, 9-12 also possible).
Function:
•
Cascading up to 8 SHE control panels cent into master-slave function.
Here, in all control panels, except for the last slave control panel the dip switches 4 and 8 set to ON.
At the last slave SHE control panel the DIP switches 8 is set to OFF.
DIP-Switch activation
When the settings of the DIP-Switches are complete the 230 V AC mains voltage is switched on or connected, as is the
emergency power battery.
•
The new functions are transferred to the memory.
•
For monitoring purposes a memory check is made as soon as the central control system is supplied with power
(mains and/or battery).
•
Display by means of approx. 3 secs long simultaneous lighting up of the displays -
OK
operation OK,
SHE
activation and
malfunction.
Compact control panel 4A, 4A/M und 8A, 8A/M