"Basic V - R" diagram: In some cases the solar circuit pump needs to be controlled according to
the solar radiation. For this purpose the radiation sensors S6 and S7 must be installed in the
corresponding collector levels. For control reasons, T1 must be inserted between the collector’s
collection point and bypass. The temperature sensor T2 is not required.
A functional description of
this add-on can be found on page 15.
To prevent erroneous settings, the described switch-on and switch-off values are interlocked,
this means they can be set only at a specific value to one another.
Connecting diagram:
Menu navigation: (here for the scheme 'Basic V' )
OK
Measuring values
collector
1:
°C
Operating status
collector
2:
°C
+Settings
storage
bottom:
°C
OK OK
solar-pump
Δ
:
h
Parameter
storage
max.
60°C
solar-pump
Σ
:
h
Date / Time
collector
max.
130°C
reversing valve
Δ
:
h
+Clocks
Diff. temp. solar ON
8K
reversing valve
Σ
:
h
+Service
Diff. temp. solar OFF
4K
OK
OK + Menu (2 sec.)
switch collect.
10K
System selection
-intern. heat exchanger
+speed control
Functions
OK
Links
-1storage
tank
Extras
OK
Manual operation
+1collector
-
2collector
OK
{
BasicP
......
~
BasicV
choose with OK (2sec.)
{
BasicV-AH
{
BasicV-AH-SFH
{
BasicV-AH-Ci
{
BasicV-SFH
{
BasicV-R
{
BasicV-Ci
T4
T5
R3
R4
M
S6
S7