12
3.9
Links Menu
This menu window is only shown in the menu if linking selected functions is required or
possible !!!
Important: The 'Links' menu window is part of the 'Service' menu and is therefore additionally
protected against unintentional changes. Hold the OK and Menu buttons simultaneously
for 2 seconds to open this menu window ("child-proof lock").
More detailed information on creating links is found in chapter 6.
3.10
Extras Menu
The ‘Extras' menu window contains the 'display contrast', 'factory settings' and 'delete records' option
box.
The contrast of the display can be changed with 'display contrast'. Press the OK button for 2
seconds to set the value (value flashes). You can now change the contrast with the
buttons and
save it by pressing the OK button again for 2 seconds.
Reset
the system regulator to the as supplied condition with
'factory settings
.
Please observe that individually adjusted setting parameters and selected
functions must be subsequently readjusted to the corresponding system.
Select
'factory settings'
and press the
OK
button for
2 seconds
to reset the system
regulator to the as supplied condition. For confirmation
'ok'
appears until the menu
is exited. Please contact your specialist dealer, if you are not confident enough to
configure the regulator yourself. No liability shall be assumed for any damage
caused by regulators incorrectly set!
Press the OK button for 2 seconds with 'delete records' to delete the measuring value records saved
to date (see chap 3.3). For confirmation 'ok' appears until the menu is exited.
3.11
Manual Operation Menu
Important: The 'Manual operation' menu window is part of the 'Service' menu and is therefore
additionally protected against unintentional changes. Hold the OK and Menu button
simultaneously for 2 seconds to open this menu window ("child-proof lock").
All used switch outputs for the system regulator and any connected add-
on modules – called IO boxes – (see ch. 9.1) can be switched on or off for
testing purposes (e.g. after maintenance and repair work) in the 'Manual
operation' menu window. For clarity reasons, only the displayed alarm
output (see chapter 9.3) and outputs, which are used by the applied layout
plan or selected functions.
To change an output’s switching status, select the output to be changed
and press the OK button for 2 seconds. This setting remains active until
the output is deactivated again by pressing the OK button for 2 seconds
or the 'Manual operation' submenu is exited via the Menu button.
Warning:
The regulator switches back to automatic mode after the 'Manual
operation' exiting submenu.
This means: this menu must be exited again after finishing
maintenance and repair work.
Links
...
Extras...
Manual operation...
R1 (regulator) off
R2 (regulator) off
R3 (regulator)
off
R4 (regulator)
off
R1 (IOBox1)
off
. . .
Alarm output off
M enu
OK + Menu
(2 sec)
R1 (regulator) on
R2 (regulator) off
R3 (regulator) off
OK (2 sec.)
R4 (regulator) off
OK (2 sec.)
Fig
.12:
'Manual operation'
menu