This menu window is shown in the menu only when a link of selected functions is required or
possible !!!
With the help of the 'Links' menu different functions, which access the same output can be logically
linked together. With these links the conditions for operation of an output can be programmed
individually.
The system regulator automatically detects whether several functions access the same output and
then displays these for selection in the 'Links' menu. The individual logical links were deliberately
made very simple. The system regulator provides an easy to understand linguistically-formulated logic
for programming.
The following example should display how a link can be created or
changed:
In this case the system regulator has detected two linked switch
outputs [R3 (regulator) and R4 (regulator)] and provides these for
selection. In addition to the system control, the functions thermostat 1
and Time function 1 also access the output R3. As standard (without
the links being changed) all functions of a switch output are linked
with or. In our example this would mean that system control,
thermostat 1 and Time function 1 can each activate the output R3
independently of one other.
In this example, however, R3 must be programmed so that R3
switches on when the system control requires this within a specific
time window or when a specific temperature is reached.
So the link must be changed so there is the following linguistically
formulated logic:
Switch R3 (regulator) 'on' if:
the System control wants to switch 'on' and
the Time function 1 wants to switch 'on' or
the thermostat 1 wants to switch 'on.
To move a function within the logic this must be selected by pressing
the OK button for 2 seconds (choice box flashes) and it can then be
moved up or down with the
buttons. To save the desired position
in the logic, press OK for 2 seconds (choice box no longer flashes).
To change a selected type of link (and/or) press the OK button for 2
seconds.
Note: The system regulator checks the individual link requirements in
the created sequence. Priority links (e.g. in digital technology by
brackets) have not been created to ensure operation is not
unnecessarily complicated.
Sys tem s election
Functions
Links
R3 regulator
R4 regulator
Menu
OK + Menu
(2 sec)
OK
M anual operation
R3 (regulator) 'on' , if:
Sys tem control 'on'
or
Therm os tat 1 'on' or
Tim e function 1 'on'
Menu
R3 (regulator) 'on' , if:
Sys tem control 'on' or
Therm os tat 1 'on' or
Tim e function 1 'on'
R3 (regulator) 'on' , if:
Sys tem control 'on' or
Therm os tat 1 'on' or
Tim e function 1 'on'
Therm os tat 1 'on'
R3 (regulator) 'on' , if:
Sys tem control 'on' or
Tim e function 1 'on'
or
Therm os tat 1 'on'
R3 (regulator) 'on' , if:
Sys tem control 'on' or
Tim e function 1 'on'
or
Therm os tat 1 'on'
R3 (regulator) 'on' , if:
Sys tem control 'on'
or
Tim e function 1 'on' or
Therm os tat 1 'on'
R3 (regulator) 'on' , if:
Sys tem control 'on'
and
Tim e function 1 'on' or
OK
(2 sec)
OK
(2 sec)
choice box flashes!
choice box flashes!
OK
(2 sec)