Ranger S Installation and troubleshooting
51
Note
Special current readings from the station test
Regardless of whether the station fails or turns out ok, you move on to
testing the next station in line by pushing the
ENTER
button.
Running the "Water Test"
The "water test" is a built‐in program that will activate all 100 station
identities in the system in turn. This way you can walk through the
landscape and ensure that all stations are actually pulling the valves open.
Running the test program
1 Turn the dial to
MANUAL
:
Reading
Meaning
-1mA / -1mA
There is a short on the terminal (on the controller)
Important
If you experience a short on the terminal and fix it, you
must restart the electrical test, or all following stations will
appear to have a terminal short.
-2mA / -2mA
There is a situation of overload (more than 2A for more
than five minutes.)
-3mA / -3mA
There is a blown fuse on the connect board.
Note:
There are a few special readings that you should be
aware of: