Appendix C: Replacing and Adding System
Components
This appendix includes replacement procedures for the SolarEdge system components.
NOTE
If you are permanently disassembling the installation or part of it, make sure to use the disposal
methods dictated by local regulations.
Replacing an Inverter
1. Turn OFF the Connection Unit.
2. Turn OFF the inverter ON/OFF switch, and wait until the LCD indicates that the DC voltage is safe
(<50V), or wait five minutes before continuing to the next step.
WARNING!
If you cannot see the inverter panel, or if a malfunction is indicated on the LCD panel, wait five
minutes for the input capacitors of the inverter to discharge.
Si vous ne pouvez pas voir l'écran de l'onduleur ou si un dysfonctionnement est indiqué sur l'écran
LCD, attendez cinq minutes pour que les condensateurs d'entrée de l'onduleur soient déchargés.
3. Turn OFF the AC switch at the distribution panel.
4. Turn OFF the battery auxiliary power switch and the circuit breaker switch.
5. Open the Connection Unit cover.
6. Turn the Bypass switch inside the Connection Unit to position 2, in order to maintain power to the
backed-up loads.
7. Disconnect the meter, battery, AC and DC wires from the Connection Unit.
8. Remove the screws securing the inverter to the mounting bracket and remove the inverter (with the
Connection Unit) from the mounting bracket.
NOTE
If you remove the old inverter and do not immediately install a new one,then:
o
Lock the Connection Unit in the OFF position using a lock on the switch.
o
Use insulation tape to isolate each of the AC and DC wires.
o
Seal the open conduits using duct tape.
9. Place the new inverter on the mounting bracket; insert the screws securing the inverter to the
mounting bracket.
10. Connect all the wires to the inverter: Follow the instructions of
30 and
Commissioning the Installation
11. Configure the system to the required application as described in
9V Battery Replacement
If Warning 8:
Connection Unit Low 9V Battery
is displayed in the main status screen, replace the 9V
battery in the Connection Unit.
SolarEdge
-
StorEdge Installation Guide MAN-01-00262-1.3
104
Appendix C: Replacing and Adding System Components