SE7600A-US
1
Unit
Lower Power Output
Higher Power Output
Revenue Grade Data, ANSI C12.1
Optional
2
Integrated AC, DC and Communication
Connection Unit
Yes
AC Disconnect
Yes
Manual Inverter Bypass Switch
Yes
DC Voltage Rapid Shutdown (PV and
Battery)
Yes, according to NEC 2014 and 2017 690.12
Auto-transformer thermal protection
Yes
STANDARD COMPLIANCE
Safety
UL1741,UL1741 SA, UL1699B, UL1998, CSA 22.2
Grid Connection Standards
IEEE1547, Rule 21, Rule 14H
Emissions
FCC part15 class B
INSTALLATION SPECIFICATIONS
AC Output (Loads/Grid) conduit size /
AWG range
1” / 14-6 AWG
in/AWG
AC Output (Backup) conduit size / AWG
range
0.75-1” drill guides / 14-6 AWG
in/AWG
AC Input (Auto-transformer) conduit size
/ AWG range
0.75-1 ” / 14-6 AWG
in/AWG
DC Input (PV) conduit size / AWG range
0.75 ” / 14-8 AWG
in/AWG
DC Input (Battery) conduit size / AWG
range
0.75” / 12-10 AWG
in/AWG
Dimensions with Connection Unit
(HxWxD)
37 x 12.5 x 7.2 / 940 x 315 x 184
in / mm
Weight with Connection Unit
58.5 / 26.5
lb / kg
Cooling
Natural convection and internal fan (user replaceable)
Noise
< 50
dBA
Min - Max Operating Temperature
-13 to +140 / -25 to +60
°F / °C
Protection Rating
NEMA 3R
1
These specifications apply to inverters with part numbers SE7600A-USS2XXXXX and connection unit model number
BCU-1PH-USS.
2Revenue grade inverter P/N: SE7600A-USS20NNM2
SolarEdge
-
StorEdge Installation Guide MAN-01-00262-1.3
112
StorEdge Inverter
Содержание SE7600A-US
Страница 1: ...SolarEdge StorEdge Solution with Backup Installation Guide For North America Version 1 3...
Страница 116: ......