StorEdge-related Errors Codes
This section describes the error messages that are specific to the StorEdge solution. For
troubleshooting errors that are not listed below, refer to
contact SolarEdge support. For the general
SolarEdge troubleshooting refer to the codes in the previous section.
Error code
LCD message
Cause and Troubleshooting
CPU v3.18
and below
CPU v3.19
and above
178
3x6D
Internal RGM Error
Check the CTs connections and direction.
179, 180
2xB3, 2xB4
Backup Consumption
Too High
Inverter production stopped due to backed-up loads’
consumption exceeding product rating.
Shutdown non-essential loads to reduce power
consumption.
181
2xB5
Connection Unit
HW Error
Check all the communication cable between the
Connection Unit and the digital board in the inverter.
182
2xB6
Auto-Transformer
Temp. Too High
Inverter production stopped due to auto-transformer
overheating.
Shutdown non-essential loads to reduce the phase
imbalance.
If you use the inverter for on-grid applications only
(without auto-transformer) - move SW2 to the
UP position (ON) (refer to
38).
183
2xB7
Connection Unit
Communication Error
There is a faulty wire connection or an internal error.
o
Check the communication cable between the
Connection Unit and the digital board in the
inverter.
o
Check that the Connection Unit LEDs are ON.
184
2xB8
Connection Unit
Temp. Too High
Inverter production stopped due to Connection Unit
overheating or due to internal fan malfunction.
o
Clean the Connection Unit fan
o
If the fan is malfunctioning, replace the fan
185
3x6B
Meter Comm. Error
186
3x6B
Battery Comm Error
o
Check the wiring to the battery and the battery
DIP switch configuration (refer to
on page 34 and
o
o
Check the battery setup in the RS485-Conf screen
(refer to
Configuring the RS485 Bus for Battery
SolarEdge
-
StorEdge Installation Guide MAN-01-00262-1.3
100
StorEdge-related Errors Codes