Table 24: Information and Actions Required for the Prompt Window
Prompt Window
Explanation
Turn On/Off:
Turn On UPS
Cancel
When you press the ON/OFF-button while UPS is Off�
Turn On/Off:
Turn On INV
Turn Off UPS
When you press the ON/OFF-button while UPS is operating on bypass mode�
Turn On/Off:
Transfer to Bypass
Cancel
When you press the ON/OFF-button while UPS is operating on inverter mode and bypass is qualified�
Turn On/Off:
Turn Off UPS
Cancel
When you press the ON/OFF-button while UPS is operating on inverter mode and bypass is not qualified�
Enter password
*******
After the control password is changed, you are required to enter the password when you want to enter
“Settings,” “Battery set” and “Service” screens�
Output must be Off
While the UPS output is supplying power, this prompt appears when you want to set some key system
parameters� You need to close the output before setting key parameters�
On manual bypass
can’t turn Off the load
This prompt appears when UPS operates on manual bypass and the ON/OFF button is pressed�
Please verify output settings before
starting the UPS
Escape: Ignore this message
Enter: Go to Settings Screen
After the UPS is powered on, When you press the ON/OFF button for the first time, this prompt appears to
remind you of viewing relevant setting�
Short Circuit Recovery
After the UPS output short circuits, wait 30 seconds before turning On the UPS again�
System is not ready
When the power modules in the frame is initializing or there are no power modules, this prompt appears
when you press the ON/OFF button�
AC input not qualified,
cannot start UPS
When the input voltage cannot meet the startup condition of the inverter, this prompt appears when you
press the ON/OFF button�
Please check air filter
When you set “Enabled” for “Air filter reminder,” this prompt appears after the reminder time is up�
Removal of module will result
in loss of output power
When only one of the system monitor module OR system control module is installed and active, when the
locking level is moved to the unlock position, this prompt appears to remind user of loss of output power will
occur if the module is removed from the system�
New Alarms Present
Escape: Ignore this message
Enter: Go to Alarms Screen
This prompt appears when a new alarm occurs�
Warning! Frame Fan Fault
Reduce load or replace fan
to avoid damage to bypass
This prompt appears when frame fan is in fault and load is heavy, user should reduce load or replace fan�
Bypass source not qualified
Can not switch to bypass
This prompt appears when bypass source is not qualified and inverter can’t power on the load for transformer
based frame�
S5KC SERIES USER MANUAL | 59