![background image](http://html.mh-extra.com/html/sola-hd/s5kc/s5kc_user-manual_1312925079.webp)
SolaHD S5KC specifications (
continued
)
10 Bay
16 Bay
12 Bay
16 Bay
10 Bay
16 Bay
Unit Size, Type
No Transformer
Transformer-based
No Transformer Dual Inverter
Frame Rating, kVA/
kW
15/13.5
20/18
15/13.5
20/18
15/13.5
20/18
Battery Module
Lead-Acid Batteries
Per String
12
Battery Cells Per String
72
Battery Capacity
36W @ 15min-rate to 1�67V per cell @25°C (77°F)
Backup Time, Full Load
5 minutes (for non-redundant system which has equal number of battery strings and power modules)
Maximum Charge
Current
(Full, Load)
Power Module Internal Charger: 1�8A
Charger Module: 10A
Nominal Voltage
144VDC
Recharge Time
< 5 Hr�to 90% capacity (PM internal charger with 1:1 ratio of PM to Battery Strings)
Output Data
Output Voltage, VAC
200/208/220/230/240
Single-Phase
100/100/173/200
110/110/190/220
115/115/199/230
120/120/208/240
Single-Phase
200/100, 220/110, 230/115,
240/120, 254/127, 208/120,
173/100, 190/110, 200/115,
220/127; Two-Phase
Voltage Regulation
±3%
Voltage Stability
(100% Step Load)
±7%
Voltage Recovery Time
≤ 60 ms
Voltage Distortion
≤ 3, linear load
≤ 5%, non-linear load
≤ 7%, non-linear load
≤ 5%, non-linear load
Output Frequency
50/60 Hz
Output Overload
Capability
< 104% continuous
105% - 130% for 1 min
131% - 150% for 10 sec
151% - 200% for 1 sec
> 201% for 250 msec
70 | 7�0
SPECIFICATIONS
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]