IntelliSlot MultiPort Card (IS-MULTIPORT)
Provides dry contact alarm information, including: On Battery, Low Battery signals for communication to four servers for
use with MultiLink software�
IntelliSlot EBC Card
This card is used for the SolaHD S5KC UPS to monitor and manage the intelligent battery modules in external matching
battery cabinets�
3.2 Dry Contact Ports
The UPS provides dry contact ports� See
Figure 1
for location and
Figure 46
for the pin layout�
Figure 46: Pin layout of the dry contacts
Table 14
shows the pin definition of each dry contact port�
Battery Mode Dry Contact
Pins 1 and 2:
Output dry contact, normally open� The dry contact is closed when the UPS is operating on battery� The
maximum voltage and current are 24VDC and 0�3A, respectively�
Low Battery Dry Contact
Pins 3 and 4:
Output dry contact, normally open� When the UPS is operating on battery, the dry contact is closed upon
battery low voltage alarm� The maximum voltage and current are 24VDC and 0�3A, respectively�
Any Mode Shut Down
Pins 5 and 6:
Input dry contact, normally open� After the external dry contact is closed (shorted), the UPS output will be
shut down during any mode of operation (mains, battery, bypass)�
1
2
3
4
5
6
7
8
Table 14: Pin Definition of Dry Contact Port
Position
Name
Description
1
Battery Mode
Output dry contact of battery mode operation
2
Battery Mode
Output dry contact of battery mode operation
3
Low Battery
Output dry contact of low battery operation
4
Low Battery
Output dry contact of low battery operation
5
Any Mode Shut Down
Input dry contact of any mode shut down
6
GND
Any mode shutdown GND
7
Battery Mode Shut Down
Input dry contact of battery mode shut down
8
GND
Battery mode shutdown GND