Configuring the Neutral/Earth Jumper
The UPS contains an isolation transformer that generates a neutral conductor for the connected load� The UPS is a
separately derived source and contains a neutral/earth jumper� A factory-installed neutral/earth jumper copper bar may
require removal to comply with local codes and regulations�
Figure 36: Configuring the neutral/earth jumper
Connecting Cables
To connect the cable:
NOTE
Input and output cables must be run in separate conduit before cable connection.
1. Remove the knockouts at the junction box (see Figure 37) and pull the cables through them, leaving some slack for
installation�
Figure 37: Knockouts
2. Connect the cable to the corresponding terminal of the power input and output terminals� Using a torque wrench,
tighten the screws to 12�43Nm (110 in-lb)� The connections are shown in
Figure 38.
16-Bay SolaHD S5KC
With Transformer
Output Cable Knockout
Input Cable Knockout
12-Bay SolaHD S5KC
With Transformer
Output Cable Knockout
Input Cable Knockout
Neutral/Earth Jumper
Neutral/Earth Jumper
1
2
30 | 2�0
INSTALLATION