8.9. Installation of MSD
Installation of Manual Switch Disconnector (MSD) shall be conducted only after the installation of DC power and control
cabling in all B-Cabs.
1. Ensure the isolation switch QS is in OFF state, refer to Figure 47.
2. Open the right-hand side battery cabinet enclosure.
3. Install the provided four MSD upper covers on the panel of each module box per the following procedure.
Note: the battery modules in the cabinet are shipped with the MSD covers uninstalled as a safety precaution.
Figure 68. MSD covers installed in the battery modules