SUNSYS HES L - 551697A - SOCOMEC
110
EN
17.2. SUN-HES-L-480
SUN-HES-L-480
(Cabinet)
+ 1÷6 x
SUN-HES-MOD50
(Power modules)
Parameters
50 kW
100 kW
150 kW
200 kW
250 kW
300 kW
DC Section
Range of DC operating voltage
570÷860 Vdc
Number of power modules
1
2
3
4
5
6
Maximum discharging current
87 A
174 A
261 A
348 A
435 A
522 A
Maximum charging current
82 A
165 A
248 A
330 A
413 A
495 A
Battery Section
Li-Ion, Lead acid, Vanadium Redox,
SuperCap, LIC, Electronic DC source,
Generic Battery.
Supported in combination with PMS.
Multi-battery compliancy through SunSpec protocol.
Please contact Socomec for specific compatibility evaluation.
AC Section
Nominal voltage (Un)
480 Vac (3ph + N)
Operating voltage range
480 Vac +/- 20% (3ph + N)
Rated frequency (Fn)
60 Hz
Operating frequency range
55 to 65 Hz
Maximum continuous Active Power
50 kW
100 kW
150 kW
200 kW
250 kW
300 kW
Maximum continuous Apparent Power
50 kVA
100 kVA
150 kVA
200 kVA
250 kVA
300 kVA
Max continuous unbalanced load
100 % of
nominal load
100 % of
nominal load
100 % of
nominal load
75 % of
nominal load
60 % of
nominal load
50 % of
nominal load
On-Grid overload
110 % - 60 minutes
(Ambient temperature dependent)
Off-grid overload (symmetrical or
asymmetrical)
110 % - 60 minutes, 125 % - 20 minutes, 150 % - 60 seconds
(Ambient temperature dependent)
Rated current
60 A
120 A
180 A
241 A
301 A
361 A
Maximum temporary current (overload)
90 A
180 A
271 A
361 A
451 A
541 A
Off-grid short-circuit current symmetrical
fault
125 A
50 ms
250 A
50 ms
375 A
50 ms
500 A
50 ms
625 A
50 ms
750 A
50 ms
Off-grid short-circuit current
asymmetrical fault (Phase to Neutral)
185 A
50 ms
370 A
50 ms
555 A
50 ms
740 A
50 ms
925 A
50 ms
1110 A
50 ms
Response time
<50ms, from 0 to 90% P/Q TBD
Output power factor rating
-1.00 to +1.00
THDI On-grid mode
< 2.5%
THDv Off-grid mode
<1.5 %
Topology
DC/AC single conversion
Parallel operation
On-grid mode
With other SUNSYS C-Cab units (power extension) or any kind of third-party generator (voltage or
current type)
Off-grid mode
With other SUNSYS C-Cab units (power extension)
With generic current/power generators
Not operated in parallel with other isochronous voltage generators
Other features
Islanding detection
Yes
Black start mode
Yes, capable of supplying the micro-grid from power cut conditions
Scheduled On-grid to Off-grid mode
transition
Yes, seamless transition without power supply break, with additional Socomec equipment. Please
contact Socomec for further information
Unscheduled On-grid to Off-grid mode
transition
Yes, with additional Socomec equipment. Please contact Socomec for further information
Synchronization of the micro-grid with
the grid to perform Off-grid to On-grid
mode transition
Yes, with additional Socomec equipment. Please contact Socomec for further information
Integrated Power Management System
services
Peak shaving, energy shifting, self-consumption, fuel saving and others on demand.