3.8. System communication
3.8.1.
Communication with external EMS
The energy exchange (charge/ discharge) of the system can be managed by an Energy Management System (EMS) that
performs remote operations.
This EMS will pilot the PMS using the Modbus TCP / SunSpec protocol.
The connection is realized with an Ethernet RJ45 cable. The C-Cab IP address will be defined during commissioning.
Socomec is member of the SunSpec organization.
The SunSpec specifications are available on the SunSpec site
https://sunspec.org/
.
Supported models
Model
Label
Description
1
Common
All SunSpec compliant devices must include this as the first model
701
DER AC Measurement
DER AC measurement model.
702
DER Capacity
DER capacity model.
703
Enter Service
Enter service model.
704
DER AC Controls
DER AC controls model.
705
DER Volt-Var
DER Volt-Var model.
706
DER Volt-Watt
DER Volt-Watt model.
713
DER Storage Capacity
DER storage capacity.
715
DER Ctl
DER Control
802
Battery Base Model
Battery Base Model
803
Li-ion Battery Bank Model
Lithium Ion Battery Model
The communication is checked by writing a heartbeat value in the 715 model, it must change every second.
To control the DER, we use the models 715 for ON/OFF controls.
The DER set points are defined by the model 704. To control the battery, we use the model 802.
Reading the model 701 you will give you access to the states, alarms and measurements.
Start sequence
Model
Offset
Name
Value
Action
Description
715
7
AlarmReset
1
Reset the alarm
715
7
AlarmReset
0
After a delay of 1 second
802
50
SetOp
1
CONNECT
Connect the battery, you have to wait the precharge before starting
the PCS
715
8
OpCtl
1
START
Start the PCS
704
22
WSetEna
1
ENABLED
Enable the active power control
704
23
WSetMod
1
WATTS
Not a percentage but a value (can be another value)
704
24
WSet
active power value
Active power set point
704
35
VarSetEna
1
ENABLED
Enable the reactive power control
704
36
VarSetMod
3
VARS
Not a percentage but a value (this setting can have another value)
704
37
VarSetPri
0
ACTIVE
This setting can have another value
704
38
VarSet
reactive power value
Reactive power set point
715
8
OpCtl
0
STOP
Stop the PCS
802
50
SetOp
2
DISCONNECT
Disconnect the battery, you have to wait 5 minutes before
switching it on again
Stop sequence
715
8
OpCtl
0
STOP
Stop the PCS
802
50
SetOp
2
DISCONNECT
Disconnect the battery, you have to wait 5 minutes before
switching it on again
Содержание SUNSYS HES L
Страница 1: ...SUNSYS HES L USER MANUAL Energy Storage System EN UL...
Страница 5: ...SUNSYS HES L 551697A SOCOMEC 5 EN...
Страница 15: ...SUNSYS HES L 551697A SOCOMEC 15 EN CHILLER SWITCHES BATTERY MODULES Figure 02 SUNSYS B Cab L composition...
Страница 114: ...551697A CORPORATE HQ CONTACT SOCOMEC SAS 1 4 RUE DE WESTHOUSE 67235 BENFELD FRANCE www socomec com...