X3-X4: Emergency stop input 1÷2 and Emergency stop output
These inputs are used to switch off the power of the C-Cab using an external emergency push button. Emergency stop
inputs shall be connected to a normally close dry contact.
If one of the input is not used, it must be short circuited.
These inputs directly control the “Emergency stop outputs”.
Emergency stop input state
Emergency stop output state
Opened
Opened
Closed
Closed
The outputs can be used to switch off the power of the C-Cab and of other C-Cabs in parallel to the first one. Each output
shall be connected to the EPO input of the Aux interface box (see “Connections to Aux interface box).
X8-X9-X10:
RS485 bus used for the communication with Diris Digiware M70 and Diris B30 devices.
The cable between X9 and X10 is pre-installed. X8 is either connected to a 120Ω
termination resistor when it’s the latest cabinet or to a C-Cab-extension if present.
8.4.4.4. Connection to automation Digiware
The two Diris Digiware modules are located in the left panel.
It is possible to connect other external Digiware current modules; this operation must be performed only by trained/
authorized personal.