8.4.3.3. AC Power connections
Concerning the AC connection, refer to Figure 50, there is enough space inside the C-Cab to connect up to 2*185mm²
/2*350MCM on each pole. The lugs needed are M12.
For ease of connection, if possible - depending on
the number of cables you are using - connect the
phases in quincunx. As shown on the drawing.
Figure 53. AC power connections positioning
Note: before connecting this power cables, connect the AC aux connection, see following chapter.