62
EN
8.4.3.4. Auxiliary power connection
Auxiliary terminals
L1L2L3 N
X107
X40
B-Cab 1...6
Figure 54. Location of the auxiliary connections in the C-Cab
Terminal block
Terminals
Description
X40
L1 L2 L3 N
AC auxiliary connection
X107
See AC aux from user’s UPS - below
AC optional auxiliary connection
B-CAB 1 ÷ B-CAB 6
See B-Cabs aux power supply - below
CATL B-Cab power supply (voltage output)
AC aux connection
Fix the wires L1, L2, L3 to the connection terminals (208 Vac Ph-Ph, 60 Hz).The neutral wire is not connected.
The maximum possible size of the cables is AWG 1 or 42.4mm².
For information, for 6 B-cabs the minimum size is AWG 2 or 33.6mm².
Note: the L1, L2 and L3 wires shall be connected respecting a
clockwise phase rotation
, i.e. L1 anticipates L2 and
L2 anticipates L3.Some utilities may adopt a counterclockwise phase rotation as standard, so the names or colors
indicated on the cables may not match the names indicated on the C-Cab AC bars.
Verify the actual phase rotation before connecting the AC cables.