DIRIS Digiware - 542875G - SOCOMEC
EN
6.4. Installing TR/iTR split-core sensors
6.4.1. Cable mounting
Install on 300 V
insulated cables only!
K
K
LL
II
Sharp edges
1
3
2
Recommended
installation:
Not recommended
Use cable ties to push
the conductor against
the base of the aperture
Do NOT clamp or pull out NON-INSULATED conductors carrying DANGEROUS VOLTAGE which could
cause an electric shock, burn or arc flash. Ref. IEC 61010-2-032.
Before closing the TR /iTR sensor, check that the air gap is clean (no contamination or corrosion).