41
DIRIS Digiware - 542875G - SOCOMEC
EN
Only use a SOCOMEC Digiware bus cable (UTP RJ45 straight, twisted pair, unshielded, AWG24, 600V CAT V
(-10 ... +70°C). When wiring, make sure you separate the low voltage (LV) section and the very low voltage (SELV)
section to prevent any risk of electric shock.
Do not pull on the RJ45 cable more than 20N.
(1)
Micro USB - type B
(2)
Do not forget to connect earth to the DIRIS Digiware U module
L1
L2
L3
(1)
(1)
(1)
(1)
I-4x
4x current
sensor inputs
I-6x
6x current
sensor inputs
Digiware Bus
Termination
DIRIS
Digiware S
DIRIS
Digiwar
e I
Curr
ent
inputs (4I)
DIRIS
Digiwar
e I
Curr
ent
inputs (6I)
DIRIS
Digiwar
e IO
Inputs/
outputs
2x digital outputs
250 VAC - 1 A max.
4 positions - screw connection,
0.25 Nm max.
0.2 mm
2
-> 2.5 mm
2
solid
0.2 mm
2
-> 2.5 mm
2
flexible
7 mm
2x digital inputs
12 VDC - 1 mA max.
3 positions - screw connection,
0.25 Nm max.
0.14 mm
2
-> 1.5 mm
2
solid
0.14 mm
2
-> 1.5 mm
2
flexible
7 mm
IO-10
4x digital inputs
12 VDC - 3 mA max.
5 screw connections,
0.25 Nm max.
2x digital outputs
48 VDC - 50 mA max.
24 VAC - 50 mA max.
4 screw connections,
0.25 Nm max.
IO-20
2x analogue inputs
0/4 - 20 mA
2x2 screw connections,
0.25 Nm max.
0.14 mm
2
-> 1.5 mm
2
solid
0.14 mm
2
-> 1.5 mm
2
flexible
7 mm
Option to connect a local
single-point display
DIRIS D-30 on the I-4x
Current sensors
TE, TR/iTR or TF