10. AUTO-DISCOVERY PROCESS
Once the system is fully wired and powered on, you must launch the auto-discovery process.
The auto-discovery process scans all slave devices connected on the Digiware and RS485 bus of the display/gateway
and assigns them with a unique Modbus address.
Two auto-discovery modes can be used:
- FAST (default mode): this mode will only detect DIRIS Digiware modules on the Digiware bus and RS485 bus,
DIRIS B and DIRIS A-40 on the RS485 bus.
- FULL: this mode will also detect other Socomec PMDs (DIRIS A) and meters (COUNTIS E) connected on the
RS485 bus.
You can launch the auto-discovery using the push button of the DIRIS Digiware M-50/M-70 gateway, using the DIRIS
Digiware D-50/D-70 display, or from the Easy Config System software.
10.1. Auto-discovery from the DIRIS Digiware M gateway
S-xx
S-135
P1
P2
S-xx
S-135
P1
P2
S-xx
S-135
P1
P2
S-xx
S-135
P1
P2
Digiware
U-xx
I-35
S-xx
Flashing LED
Stable LED
2
1
ALARM
ON
COM
ADDR.
ETH
ETH
DIRIS M-xx
ETH
DIGIWARE
BUS
24 V
20 W max
SUPPLY
RS485
NC
Press
2 sec.
ALARM
ON
COM
ETH
ETH
DIRIS M-xx
ETH
DIGIWARE
BUS
24 V
20 W max
SUPPLY
RS485
NC
≤ 120 sec
3
ADDR.
ALARM
ON
COM
ADDR.
ETH
ETH
DIRIS M-xx
ETH
DIGIWARE
BUS
24 V
20 W max
SUPPLY
RS485
NC
ALARM
ON
COM
ADDR.
ETH
ETH
DIRIS M-xx
ETH
DIGIWARE
BUS
24 V
20 W max
SUPPLY
RS485
NC
7
6
3
3
3
2
2
5
b
5
a
Press
2 sec.
4
b
4
a
Press
2 sec.