71
DIRIS Digiware - 542875G - SOCOMEC
EN
The AUTOCORRECT menu will display the following diagnostic table:
AUTOCORRECT
|
PC 1-2-3
>>
INPUT
WAY
V
P
P1
I03
+/DIRECT
V1
+
P2
I02
+/DIRECT
V2
+
P3
I01
+/DIRECT
V3
+
PRESS OK TO LAUNCH AUTOCORRECT
The table indicates that the load power P1 will be correctly calculated by associating current from the iTR
connected to input I03 with voltage V1 from the DIRIS Digiware U-xx module.
This is not the case as per the cross marks on lines P1 and P3 and the gray cells that indicate the errors are on
the INPUT I03 and I01.
• Press “OK” to launch AUTOCORRECT:
AUTOCORRECT
|
PC 1-2-3
AUTOCORRECT: SOFTWARE CORRECTION
MANUAL: PHYSICAL WIRING CORRECTION
AUTOCORRECT
Choose the power sign – “POSITIVE” for Power import (consumption) or “NEGATIVE” for Power export (generation), and
press “OK”:
AUTOCORRECT
|
PC 1-2-3
CHOOSE POWER SIGN
POSITIVE
• Now the wiring has been corrected in the software and power values are correctly calculated:
AUTOCORRECT
|
PC 1-2-3
>>
INPUT
WAY
V
P
P1
I03
+/DIRECT
V1
+
P2
I02
+/DIRECT
V2
+
P3
I01
+/DIRECT
V3
+