82
DIRIS Digiware - 542875G - SOCOMEC
EN
16.2.2. Electromagnetic compatibility and insulation levels
TF flexible sensors
Test standard
Test level
Performance
criteria
Immunity to electrostatic discharge (ESD)
IEC 61000-4-2
6kV contact – LEVEL III
8kV air – LEVEL III
B
Immunity to radiated, radio-frequency,
electromagnetic field
IEC 61000-4-3
80MHz – 1GHz: 10V/m – LEVEL III
1.4GHz – 2GHz: 3V/m - LEVEL II
2.0GHz – 2.7GHz: 1V/m – LEVEL I
A
Immunity to electrical fast transients/bursts
IEC 61000-4-4
4kV on power supply port and 2kV on input/
output signal.
B
Immunity to surges
IEC 61000-4-5
4kV Common mode, 2kV differential mode –
LEVEL IV
B
Immunity to conducted disturbances, induced by
radio-frequency fields
IEC 61000-4-6
LEVEL III
A
Immunity to power frequency magnetic fields
IEC 61000-4-8
LEVEL V
A
Radiated Emission
EN 55022
30 to 230Mhz : 30dBuV/m
230 to 1000Mhz : 37dBuV/m
B
TE/TR/iTR sensors
Test standard
Test level
Performance criteria
Immunity to electrostatic discharge (ESD)
IEC 61000-4-2
III
A
Immunity to radiated, radio-frequency, electromagnetic fields
IEC 61000-4-3
III
A
Immunity to electrical fast transients/bursts
IEC 61000-4-4
III
A
Immunity to surges
IEC 61000-4-5
Line to line : III
Line to ground : IV
A
Immunity to conducted disturbances, induced by radio-
frequency fields
IEC 61000-4-6
III
A
Immunity to power frequency magnetic fields
IEC 61000-4-8
IV
A
Radiated Emission
CISPR11
-
Class B
16.3. DIRIS D-30 - technical characteristics
16.3.1. Mechanical characteristics
Type of screen
Capacitive touch-screen technology, 10 keys
Screen resolution
350 x 160 pixels
Front panel protection index
IP65
Weight
D-30: 160 g
16.3.2. DIRIS D-30 communication characteristics
Type of screen
Local single-point screen for DIRIS Digiware I-4x
RJ9
Self-powered and data
USB
Upgrade and configuration via type B micro USB connector