84
DIRIS Digiware - 542875G - SOCOMEC
EN
17. PERFORMANCE CLASSES
17.1. DIRIS Digiware I
Performance classes are given in compliance with IEC 61557-12
Classification of DIRIS Digiware
DD in combination with dedicated sensors (TE, TR/iTR, TF)
Temperature
K55
Overall operating performance class for active power or active energy 0.5 in combination with TE, iTR or TF solid-core sensors
1 in combination with TR split-core sensors
Symbol
Description
Overall operating performance
class DIRIS Digiware I +
dedicated sensors* (TE, TR/
iTR, TF) in compliance with IEC
61557-12
Measurement
range
Pa
Total active power
0.2 DIRIS Digiware only
0.5 with TE, iTR or TF sensors
1 with TR sensors
10% … 120% In
2% … 120% In
2% … 120% In
Q
A
, Q
V
Total reactive power (arithmetic, vectorial)
2 with TR sensors
1 with TE, iTR or TF sensors
5% … 120% In
S
A
, S
V
Total apparent power (arithmetic, vectorial)
0.5 with TE, iTR or TF sensors
1 with TR sensors
10% … 120% In
Ea
Total active energy
0.2 DIRIS Digiware only
0.5 with TE, iTR or TF sensors
1 with TR sensors
10% … 120% In
2% … 120% In
2% … 120% In
Er
A
, Er
V
Total reactive energy (arithmetic, vectorial)
2 with TE, TR/iTR or TF sensors
5% … 120% In
Eap
A
,
Eap
V
Total apparent energy (arithmetic, vectorial)
0.5 with TE, iTR or TF sensors
1 with TR sensors
10% … 120% In
f
Frequency
0.02
45 - 65 Hz
I, IN
Phase current, measured neutral current
0.2 DIRIS Digiware only
0.5 with TE, iTR or TF sensors
1 with TR sensors
5% … 120% In
10% … 120% In
10% … 120% In
INc
Calculated neutral current
1 with TE, iTR or TF sensors
2 with TR sensors
10% … 120% In
U
Voltage (Lp-Lg or Lp-N)
0.2
50 - 300 VAC Ph/N
PF
A
, PF
V
Power factor (arithmetic, vectorial)
0.5 with TE, iTR or TF sensors
1 with TR sensors
0.5 lagging to 0.8
leading
Pst, Plt
Flicker (short-term, long-term)
-
-
Udip
Voltage dip (Lp-Lg or Lp-N)
0.5
-
Uswl
Voltage swell (Lp-Lg or Lp-N)
0.5
-
Uint
Voltage interruption (Lp-Lg or Lp-N)
0.2
-
Unba
Voltage amplitude unbalance (Lp-N)
0.5
-
Unb
Voltage phase and amplitude unbalance (Lp-Lg
or Lp-N)
0.2
-
THDu,
THD-Ru
Total harmonic distortion rate of the voltage
(relative to the fundamental, relative to the RMS
value)
1
Orders 1 to 63
Uh
Voltage harmonics
1
-
THDi,
THD-Ri
Total harmonic distortion rate of the current
(relative to the fundamental, relative to the RMS
value)
1 with sensors TE, TR/iTR or TF
Orders 1 to 63
Ih
Current harmonics
1 with sensors TE, TR/iTR or TF
-
Msv
Centralised remote control signals
-
-
*With SOCOMEC RJ12 and RJ45 connection cables.