5.2. Presentation of the associated current sensors
Various types of current sensors are connected to DIRIS Digiware I modules: solid-core (TE), split-core (TR/iTR) or flexible
(TF). The variety of these sensors make them suitable with any type of new, existing or high-current existing installation.
They all use a specific link with the DIRIS Digiware I current measurement module. This link ensures rapid connection
without any wiring error. DIRIS Digiware automatically recognises the type of current sensor that is connected and its
rating.. In addition, combining them means the overall accuracy of DIRIS Di Current sensor measurement chain
can be guaranteed over a large measurement range.
DIRIS Digiware
I-30 / I-31 / I-35
DIRIS Digiware
I-4x
DIRIS Digiware
I-60 / I-61
3
Current sensors
TE / TR/iTR / TF
4
Current sensors
TE / TR/iTR / TF
6
Current sensors
TE / TR/iTR / TF
For connecting the current sensors, use SOCOMEC cables or RJ12 straight cables, twisted pair, unshielded,
600 V -10°C / +70°C. It is recommended that all the current sensors be installed in the same direction.
Connection cables for current sensors:
RJ12
connection
cables
Cable length (m)
0.1
0.2
0.3
0.5
1
2
3
5
10
50 m reel
+ 100
connectors*
Number of
cables
Ref.
Ref.
Ref.
Ref.
Ref.
Ref.
Ref.
Ref.
Ref.
Ref.
1
-
-
-
-
-
-
4829 0606 4829 0602 4829 0603
4829 0601
3
4829 0580 4829 0581 4829 0582 4829 0595 4829 0583 4829 0584
-
-
-
-
4
4829 0596 4829 0588 4829 0589
-
-
-
-
6
4829 0590 4829 0591 4829 0592 4829 0597 4829 0593 4829 0594
-
-
-
-
* When producing cables, do not exceed a maximum length of 10 metres.