79
DIRIS Digiware - 542875G - SOCOMEC
EN
16.1.5. Environmental characteristics
Ambient operating temperature
-10 … +70°C (+55 °C for DIRIS Digiware S) (IEC 60068-2-1/IEC 60068-2-2)
Storage temperature
-25 … +70°C (IEC 60068-2-1/IEC 60068-2-2)
Operating humidity
25°C / 97% RH & 55°C / 93% RH (IEC 60068-2-30)
Operating altitude
< 2000 m
Vibration
0.35 mm, 25 Hz, 20 min/axe (IEC 61557-12)
Impact resistance
Front panel: 1J (5J for DIRIS Digiware S) - casing: 1J (IEC 61010-1 Ed 3.0)
PEP ecopassport - ISO 14025
DIRIS Digiware U: SOCO-2014-05-v1-fr, SOCO-2014-05-v1-en
DIRIS Digiware S: SOCO-00006-V01.01-FR; SOCO-00006-V01.01-EN
DIRIS Digiware I: SOCO-2014-06-v1-fr, SOCO-2014-06-v1-en
DIRIS Digiware IO :SOCO-00001-V01.01-fr, SOCO-00001-V01.01-en
16.1.6. Electromagnetic characteristics
Immunity to electrostatic discharges (ESD)
IEC 61000-4-2 LEVEL III
Immunity to radiated radio-frequency electromagnetic fields
IEC 61000-4-3 LEVEL III
Immunity to electrical fast transients/bursts
IEC 61000-4-4 LEVEL III
Immunity to surges
IEC 61000-4-5 LEVEL III
Immunity to conducted disturbances induced by radio-frequency fields
IEC 61000-4-6 LEVEL III
Immunity to power frequency magnetic fields
IEC 61000-4-8 400A/m
Radiated emissions
CISPR11 Group1 - CLASS B
16.1.7. Standards and safety
Device
IEC 61557-12, power metering and monitoring device (PMD)
CE
Compliant with Low Voltage Directive:
2014/35/EU of February 26th 2014 (IEC EN61010-1 & IEC EN61010-2-030).
Compliant with Electromagnetic Compatibility Directive:
2014/30/EU of February 26th 2014 (IEC EN 61326-1).
Insulation
Installation category III (300VAC Ph/N), degree of pollution 2
UL
UL 61010-1 & 61010-2-030 compliant
UL installation:
The DIRIS Digiware system must be enclosed in an NRTL certified
electrical/fire enclosure, listed Industrial Control Panel Equipment, or
similar equipment.
16.1.8. Service life
MTTF (mean time to failure)
> 100 years