-27-
No.PS
※※
-OMW0005-A
Simple Setting Mode
<Operation>
[Simple setting mode (hysteresis mode)
In the simple setting mode, the set value, hysteresis and delay time can be changed while checking the
current pressure value (main display).
(1) After selecting the channel, press the SET button for 1 second or longer, but less than 3 seconds, in
measurement mode. [SEt] is displayed on the main display.
When the button is released while in the [SEt] display, the current pressure value is displayed on the
main display, [P_1] or [n_1] is displayed on the sub display (left), and the set value is displayed on the
sub display (right) (Flashing).
(2) Change the set value with UP or DOWN button, and press the SET button to set the value. Then, the
setting moves to hysteresis setting. (The snap shot function can be used. (Refer to page
))
(3) Change the set value with UP or DOWN button, and press the SET button to set the value. Then, the
setting moves to the delay time of the switch output.
(The snap shot function can be used. (Refer to page
(4) The delay time of the switch output can be selected by pressing the UP or DOWN button at the ON and
OFF point of the switch output.
Delay time setting can prevent the output from chattering.
The delay time can be set in the range 0.00 to 60.00 sec. in 0.01 sec. increments.
(5) Press the SET button for 2 seconds or longer to complete the OUT1 setting.
[P_2] or [n_2] is displayed on the sub screen (left). Continue with setting the OUT2.
Press and hold the SET button for 2 seconds or longer to complete the setting. The product will return to
measurement mode.
1: Selected items (1) to (4) become valid after pressing the SET button.
2: After enabling the setting by pressing the SET button, it is possible to return to measurement mode by pressing the SET button
for 2 seconds or longer.
3: When the output mode (refer to page
) is set to error output or switch output OFF, the simple setting mode cannot be used.