Other Settings
○Channel scan function
•Press the UP button for 2 seconds or longer. Channels and the measured pressures will be displayed in
order approximately every 2 seconds.
•The function can be released by pressing the UP button again for 2 seconds or longer.
: Channel scan function will remain even when the power supply is turned off.
: During channel scan, setting is disabled other than channel scan mode release and key lock function setting.
Release the channel scan mode when changing settings.
○Snap shot function
The current pressure value can be stored to the switch output ON/OFF set point.
When the items of sub display (left) below are selected in 3 step setting mode, simple setting mode or
function selection mode ([F 1] Setting of OUT1, [F 2] Setting of OUT2), by pressing the UP and DOWN
buttons simultaneously for 1 second or longer, the value of the sub display (right) shows [- - -], and the
values corresponding to the current pressure values are automatically displayed.
Output mode
Configurable items
Sub display (left)
Snap shot function
Hysteresis mode
Set value
(
)/
(
)
○
Hysteresis
/
○
Window comparator mode
Set value
(
),
(
)
(
),
(
)
○
Hysteresis
/
×
•Set value
The value is set to the same value as the display value (current pressure value).
(There is a range which cannot be set to the current pressure depending on the hysteresis. In that case, the
value is set to the closest value.)
•Hysteresis
The hysteresis is calculated from the equation below and set.
Normal output: (set value) - (current pressure value)
Reverse output: (current pressure value) - (set value)
If the calculation result becomes 0 or less, [Err] is displayed on the sub display (right) and the set value is
not changed.
Afterwards, it is possible to adjust the value by pressing the UP or DOWN button.
○Peak/bottom value indication
The maximum (minimum) pressure when the power is supplied is detected and updated.
In peak/bottom indication mode, the current pressure is displayed.
Press the DOWN button in measurement mode to switch the sub-display (left) to the display shown below.
Peak/bottom values are displayed on the sub display (right) at the same time as the current pressure value
on the main display.
When the SET and DOWN buttons are pressed for 1 second or longer simultaneously while the peak/bottom
values are displayed, the sub display (right) displays [- - -] and the maximum (minimum) pressure value are cleared.
: Peak/ bottom value are not stored to memory.