-29-
No.PS
※※
-OMW0005-A
Function Selection Mode
■
Function selection mode
After selecting the channel, in measurement mode, press the S button for 3 seconds or longer (but less than
5 seconds), to display [F 0].
Select to display the function to be changed [F
□□]. Press and hold the SET button for 2 seconds or longer in
function selection mode to return to measurement mode.
: Some products do not have all the functions. If no function is available or selected due to configuration of other functions, [- - -] is
displayed on the sub display (right).
: All channel indicators turn on for the setting which is common for all channels.
■
Default setting
The default setting is as follows.
If no problem is caused by this setting, keep these settings.
To change a setting, enter function selection mode.
●
[F 0] Differential pressure check mode, pressure range and display unit
Item
Default setting
Differential pressure check mode
OFF
Connected sensor range
Vacuum pressure
Display units
Units specification ["Nil" or M]: [kPa]
●
[F 1] Setting of OUT1
Item
Explanation
Default setting
Output mode
Either hysteresis mode, window comparator mode, error output
or switch output OFF can be selected.
Hysteresis mode
Reversed output
Selects which type of switch output is used, normal or reversed.
Normal output
Pressure setting
Sets the ON and OFF point of the switch output.
-50.5 kPa
Hysteresis
Appropriate setting of the hysteresis will prevent the switch
output from chattering.
5.1 kPa
Delay time
Delay time of the switch output can be selected.
0.00 sec.
Display colour
Select the display colour.
Output ON : Green
Output OFF: Red
(Linked to OUT1)