-OMW0005-A
■
[F14] Zero cut-off setting
When the pressure display value is close to zero, the product rounds the value and zero will be displayed.
The zero cut-off range is 0.0 to 10.0% F.S., and can be set in 1.0% F.S. increments.
: Zero-cut setting cannot be selected when auto-shift zero is set.
<Operation>
Press the UP or DOWN button in function selection mode to display [F14].
Press the SET button.
Move on to select zero cut-off setting.
Select zero cut-off setting
Press the UP or DOWN button to select the value of zero cut-off.
: The display above is an example when 1 MPa range and unit selection function are [MPa] selected.
: When the actual pressure is smaller than the displayed value in the upper line, zero will be displayed.
Example:
1 MPa range P_1 = 0.015 [MPa], H_1 = 0.01 [MPa], zero cut-off 1.0%
Press the SET button to set.
Return to function selection mode.
[F14] Zero cut-off setting completed