-35-
No.PS
※※
-OMW0005-A
Setting of the lower limit of the additional
rated range
Press the UP or DOWN button to change the
value.
Press the button continuously to keep changing
the value.
Set the value that is required to be displayed
when the sensor input signal is 0%.
The setting range is -1500 to 1500 digit.
: There is unsettable range. (Refer to page
Press the SET button to set.
Setting of the upper limit of the additional
rated range
Press the UP or DOWN button to change the
value.
Press the button continuously to keep changing
the value.
Set the value that is required to be displayed
when the sensor input signal is 100%.
The setting range is -1500 to 1500 digit.
: There is unsettable range. (Refer to page
Press the SET button to set.
Move on to display unit setting.
Display unit setting
Press the UP or DOWN button to select the display unit.
: The unit that can be displayed is different depending on the pressure range. (Refer to page
(kPa/MPa/Pa can still be selected if the product does not have the units selection function.)
: Refer to page
for LCD of corresponding unit.
Press the SET button to set.
Return to function selection mode.
[F0] Setting of differential pressure check mode, pressure range and display unit is completed
Move on to the setting of the upper limit
of the additional rated range.
The upper limit of the rated range is the
displayed value when the sensor input
signal is 100%.