[F 0] Differential pressure check mode, pressure range and display unit
<Differential pressure check mode>
Selected channel is CH1: Differential pressure between CH1-CH2 can be set and displayed.
Selected channel is CH2: Measurement value of CH2 (normal operation) can be set and displayed.
Selected channel is CH3: Differential pressure between CH3-CH4 can be set and displayed.
Selected channel is CH4: Measurement value of CH4 (normal operation) can be set and displayed.
Selected channel
CH1
CH2
CH3
CH4
Normal operation mode
CH1
CH2
CH3
CH4
Differential pressure check mode
CH1-CH2
CH2
CH3-CH4
CH4
Output
CH1_OUT1
CH1_OUT2
CH2_OUT1
CH3_OUT1
CH4_OUT1
Channel display
CH1/CH2
ON
CH2
ON
CH3/CH4
ON
CH4
ON
: When differential pressure check mode is selected, the range of the sensor connected to CH1-CH2 and CH3-CH4 should be the
same.
: Initial range setting [rAnG] and unit setting [Unit] and digital filter [FiL] for CH2 and CH4 are not selectable. The operations are based
on the setting for CH1 and CH3.
: Set pressure range during differential pressure check mode is the same as the normal operation mode.
:
During differential pressure check mode, measurement error “[- - -]” is displayed when the applied pressure error ([HHH], [LLL])
occurs in one or both selected channel(s).
Refer to the connection in the table below for connecting the sensor for differential pressure check mode.
Set range can be effectively used by connections below.
Range setting
Selected channel
CH1
CH2
CH3
CH4
Compound pressure
Hi/Lo side
Lo/Hi side
Hi/Lo side
Lo/Hi side
Vacuum pressure
Lo side
Hi side
Lo side
Hi side
Low pressure/
Positive pressure/High pressure
Hi side
Lo side
Hi side
Lo side
: Hi: High pressure side, Lo: Low pressure side.