Chapter 5 Display and setting of various functions
5.20
Alarm customizing function
HRS Series
5-54
Setting/Checking: Threshold temperature setting for "Detection temp. for the circulating fluid discharge temp. increase" alarm
6.
Press the [SEL] key once.
Threshold detecting temperature setting screen for "Circulating fluid discharge temp.
rise" alarm generation appears on the digital display.
PV
SV
7.
Set the threshold detection temperature for "Circulating fluid discharge temp. rise" alarm
generation with [
▲
] key or [
▼
] key, and press [SEL] key to enter.
Table 5.20-10 Threshold detection temperature setting for "Circulating fluid discharge temp. rise" alarm generation
Set value
Explanation
Initial value
(Default setting)
Setting/checking of the alarm is impossible
when the "Circulating fluid discharge temp.
rise" alarm is set OFF.
Centigrade
to
Fahrenheit
to
Sets threshold detecting temperature for
“Circulating fluid discharge temp. rise” alarm.
Setting temperature unit for Centigrade: 0.1
o
C
Setting temperature unit for Fahrenheit: 0.1
o
F
Setting/Checking: Operation setting when "Circulating fluid discharge temp. drop" alarm is generated
8.
Press the [SEL] key once.
Operation setting screen when "Circulating fluid discharge temp. drop" alarm is
generated appears on the digital display.
Set the product operation when "Circulating fluid discharge temp. drop" alarm is
generated with [
▲
] key or [
▼
] key, and press [SEL] key to enter.
PV
SV
9.
Set the product operation when "Circulating fluid discharge temp. drop" alarm is
generated with [
▲
] key or [
▼
]key, and press [SEL] key to enter.
Table 5.20-11 Operation setting when “Circulating fluid discharge temp. drop” alarm is generated
Set value
Explanation
Initial value
(Default setting)
This alarm is not detected.
Operation continues when this alarm is
generated.
✓
Operation stops when this alarm is generated.
Содержание HRS090-A
Страница 8: ...HRX OM S004 Contents HRS Series...
Страница 20: ...HRX OM S004 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRS Series 2 6...
Страница 56: ...HRX OM S004 Chapter 3 Transport and Setting Up 3 5 Circulating Fluid Supply HRS Series 3 36...
Страница 66: ...HRX OM S004 Chapter 4 Starting the Product 4 6 Adjustment of Circulating Fluid flow rate HRS Series 4 10...
Страница 164: ......
Страница 174: ......
Страница 192: ...HRX OM S004 Chapter 8 Documents 8 9 Daily Check Sheet HRS Series 8 18...
Страница 195: ......