HRX-OM-S004
Chapter 5 Display and setting of various functions
HRS Series
5.20
Alarm customizing function
5-51
Table 5.20-6 Default settings of the alarm customizing function (2/3)
Object alarm
Display
Content
Code
Alarm name
Change content
Default
setting
Operation setting when
"DC line fuse cut" alarm is
generated
AL21
DC line fuse cut
Product operation
while the alarm is
being generated
A.STP
AL03
Circulating fluid
discharge temp. rise
Temperature alarm
monitoring mode setting
AL04
Circulating fluid
discharge temp. drop
Monitoring method
0
AL03
Circulating fluid
discharge temp. rise
Monitoring start timer
AL04
Circulating fluid
discharge temp. drop
Alarm will not be
generated during the
set period of time after
starting operation.
Alarm monitoring starts
when the set time has
passed.
----
(0)
AL03
Circulating fluid
discharge temp. rise
Range over detection
timer
AL04
Circulating fluid
discharge temp. drop
An alarm will not be
generated for the set
period of time after the
circulating fluid
discharge temperature
becomes out of the set
range.
5
AL10
High compressor intake
temp.
AL11
Low compressor intake
temp.
AL12
Low super heat temp.
AL13
High compressor
discharge pressure
AL15
Refrigerant circuit
pressure (high pressure
side) drop
AL16
Refrigerant circuit
pressure (low pressure
side) rise
AL17
Refrigerant circuit
pressure (low pressure
side) drop
AL18
Compressor running
failure
AL24
Compressor intake
temp. sensor failure
AL26
Compressor discharge
pressure sensor failure
AL27
Compressor intake
pressure sensor failure
AL37
Compressor discharge
temp. sensor failure
AL38
Compressor discharge
temp. rise
AL43
*2
Fan failure
Compressor stop alarm
AL45
Compressor over
current
Alarm operation
P.RUN
∗
2: This alarm does not occur on the product of water cooled type.
Содержание HRS090-A
Страница 8: ...HRX OM S004 Contents HRS Series...
Страница 20: ...HRX OM S004 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRS Series 2 6...
Страница 56: ...HRX OM S004 Chapter 3 Transport and Setting Up 3 5 Circulating Fluid Supply HRS Series 3 36...
Страница 66: ...HRX OM S004 Chapter 4 Starting the Product 4 6 Adjustment of Circulating Fluid flow rate HRS Series 4 10...
Страница 164: ......
Страница 174: ......
Страница 192: ...HRX OM S004 Chapter 8 Documents 8 9 Daily Check Sheet HRS Series 8 18...
Страница 195: ......