HRX-OM-S004
Chapter 5 Display and setting of various functions
HRS Series
5.16
Accumulated Operating Time Reset Function
5-39
Reset of the accumulated operating time of the dust-proof filter
10.
Press and hold the [MENU] key for approximately 2 seconds.
Repeat pressing the key until the button-lock setting screen [
] appears on the
digital display.
PV
SV
PV
SV
PV
SV
11.
Press the [SEL] key 29 times.
Resetting screen of the accumulated operating time of the dust-proof filter appears on
the digital display.
PV
SV
12.
Select
with [
▲
] key or [
▼
] key, and press
[SEL] key to enter. Select
and press [SEL] key to enter, and the accumulated operating time of the
dust-proof filter will be reset. The display returns to the main menu.
Table 5.16-5 Reset setting
Set value
Explanation
Default
No data reset.
✓
Resets the accumulated operating time of the
dust-proof fiter.
Press and
hold [MENU]
key.
Press and
hold [MENU]
key.