HRX-OM-S004
Chapter 6 Alarm Notification and Troubleshooting
6.3
Troubleshooting
HRS Series
6-6
Table 6-2 Alarm codes and troubleshooting (2/3)
Code
Alarm name
Alarm
operation*1
(Default
setting)
Cause / Remedy
(Press the reset key after eliminating the
cause.)
AL18
Compressor running
failure
P.RUN
Leave it for 10 minutes, and then restart the
thermo-chiller. Check if the pump operates.
AL19
Communication error
OFF
Try to send the request message again.
AL20
Memory error
A.STP
Controller failure.
Ask for service for the controller.
AL21
DC line fuse cut
A.STP
Fuse for the power supply output of the contact
input/output connector has blown.
・
Ask for service for the fuse of the output voltage
circuit.
・
Check that there is no incorrect wiring and the
current load is within the specified range.
AL22
Circulating fluid
discharge temp. sensor
failure
A.STP
AL23
Circulating fluid return
temp. sensor failure
A.STP
AL24
Compressor suction
temp. sensor failure
P.RUN
Short-circuit or broken wire of the temperature
sensor.
Ask for service for the temperature sensor.
AL25
Circulating fluid
discharge pressure
sensor failure
A.STP
Short-circuit or broken wire of the pressure sensor
of the circulating fluid circuit. EEEE is displayed on
the PI display of the main display and check
monitor display.
Ask for service for the pressure sensor.
AL26
Compressor discharge
pressure sensor failure
P.RUN
AL27
Compressor suction
pressure sensor failure
P.RUN
Short-circuit or broken wire of the pressure sensor
of the refrigerant circuit. Ask for service for the
pressure sensor.
AL28
Pump maintenance
OFF
Every 20,000
hours
AL29
Fan maintenance
OFF
Every 30,000
ours
AL30
Compressor
maintenance
OFF
Notices of the periodical
maintenances.
Ask for services of the pump, fan
and/or compressor.
Reset the operation cumulated
time for each alarm with the
menu SE.15, SE.16 or SE.17
after having the service.
Every 30,000
hours
AL31
Contact input 1 signal
detection
A.STP
AL32
Contact input 2 signal
detection
A.STP
Contact input has been detected.
AL37
Compressor discharge
temp. sensor failure
P.RUN
Short-circuit or broken wire of the temperature
sensor. Ask for service for the temperature sensor.
AL38
Compressor discharge
temp. rise
P.RUN
Check that the ambient temperature, facility water,
and heat load satisfy the specifications.
AL40
∗
1
Dust-proof filter
maintenance
OFF
Notice of the periodical
maintenance.
Clean the dust-proof filter. Reset
the operation cumulated time for
the alarm with the menu SE.30
after cleaning the filter. This
alarm can be OFF with the menu
AS.29.
1 to 9999
hours
(AS.31)
*1: Water-cooled type model does not generate this alarm.
Содержание HRS090-A
Страница 8: ...HRX OM S004 Contents HRS Series...
Страница 20: ...HRX OM S004 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRS Series 2 6...
Страница 56: ...HRX OM S004 Chapter 3 Transport and Setting Up 3 5 Circulating Fluid Supply HRS Series 3 36...
Страница 66: ...HRX OM S004 Chapter 4 Starting the Product 4 6 Adjustment of Circulating Fluid flow rate HRS Series 4 10...
Страница 164: ......
Страница 174: ......
Страница 192: ...HRX OM S004 Chapter 8 Documents 8 9 Daily Check Sheet HRS Series 8 18...
Страница 195: ......