HRX-OM-S004
Chapter 4 Starting the Product
HRS Series
4.5
Check items during startup
4-9
4.5 Check items during startup
Check the following items after starting the product.
z
Confirm that there is leakage from the piping.
z
Confirm that no circulating fluid is discharged from the pump drain port.
z
Confirm that the circulating fluid pressure is within the specification range.
z
Confirm that the fluid level shown by the fluid level gauge is within the
specification range.
4.6 Adjustment of Circulating Fluid flow rate
When the circulating fluid flow rate is smaller than the minimum required,
the product may fail to maintain the performance. And there is possibility of
occurring overload of the pump.
Refer to
Fig. 3-18 Recommended piping circuit, and adjust the flow rate with the
manual valve to the required pressure or flow rate while monitoring the pressure
and/or flow rate.
[Tips]
Regarding the minimum operation flow rate, refer to “8.1 Specifications”.
When any abnormality is found, press the [STOP] button to stop the
product operation, and then turn OFF the breaker of the user’s power
supply.
Содержание HRS090-A
Страница 8: ...HRX OM S004 Contents HRS Series...
Страница 20: ...HRX OM S004 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRS Series 2 6...
Страница 56: ...HRX OM S004 Chapter 3 Transport and Setting Up 3 5 Circulating Fluid Supply HRS Series 3 36...
Страница 66: ...HRX OM S004 Chapter 4 Starting the Product 4 6 Adjustment of Circulating Fluid flow rate HRS Series 4 10...
Страница 164: ......
Страница 174: ......
Страница 192: ...HRX OM S004 Chapter 8 Documents 8 9 Daily Check Sheet HRS Series 8 18...
Страница 195: ......