HAT600P Series ATS Controller User Manual Page 27 of 58
No.
Item
Range
Default
Description
Bit6: July
Bit7: August
Bit8: September
Bit9: October
Bit10: November
Bit11: December
5
Schedule Date
(1~31)
1
Date of genset start in every month;
6
Schedule Weekly
(1~127)
1
Bit0: Sunday
Bit1: Monday
Bit2: Tuesday
Bit3: Wednesday
Bit4: Thursday
Bit5: Friday
Bit6: Saturday
7
Schedule Hours
(0~23)h
0
Scheduled start time;
8
Schedule Minutes
(0~59)min
0
9
Schedule Work
Time
(0~30000)min
30
The lasting time for scheduled start
running;
10
Gen Inhibit Work
(0~1)
0
0: Disable
1: Enable
11
Inhibit Period
(0~2)
0
0: Monthly
1: Weekly
2: Daily
12
Inhibit Monthly
(1~4095)
4095
Bit0: January
Bit1: February
Bit2: March
Bit3: April
Bit4: May
Bit5: June
Bit6: July
Bit7: August
Bit8: September
Bit9: October
Bit10: November
Bit11: December
13
Inhibit Date
(1~31)
1
Date of not start in every month;
14
Inhibit Weekly
(1~127)
1
Bit0: Sunday
Bit1: Monday
Bit2: Tuesday
Bit3: Wednesday
Bit4: Thursday
Bit5: Friday
Bit6: Saturday
15
Inhibit Hours
(0~23) h
0
Time for scheduled non-start;
16
Inhibit Minutes
(0~59) min
0
17
Inhibit Rest Time
(0~30000) min 30
The lasting time for scheduled
non-start;
Load Settings
1
Current CT Enable
(0~1)
1
0: Disable
1: Enable
2
CT Primary
(5~6000)A
500
Primary Current of CT;
3
S1 Full Load Rating
(5~6000)A
500
Current of S1 full load;
4
S2 Full Load Rating
(5~6000)A
500
Current of S2 full load;
5
S1 Max kW Rating
(1~20000)kW
200
Max. active power of S1 full load;
6
S2 Max kW Rating
(1~20000)kW
200
Max. active power of S2 full load;