HAT600P Series ATS Controller User Manual Page 31 of 58
No.
Item
Range
Default
Description
11
Controller
Information 1
(0-20)
characters
Information displayed in ABOUT page;
Users can input any character (letter is
1 character; while Chinese character is
2 characters), and it needs to set on PC
by software;
12
Controller
Information 2
(0-20)
characters
Network Settings
1
Network Enable
(0~1)
1
0: Disable
1: Enable
2
IP Address
192.168.0.100
ETHERNET communication
parameters;
3
Subnet Mask
255.255.255.0
4
Gateway
192.168.0.1
5
Sensor Curve Type
Set through PC software
9.3
DIGITAL INPUT PORT FUNCTION DESCRIPTION
Table 19 Input Port Function Description
No.
Item
Description
0
Not Used
Invalid
1
Forced Open
It (Non-firefighting cutoff input) is only suitable for switches with
breaker control; when it is active, switches shall changeover to
neutral no matter in manual mode or in auto mode.
2
Remote Start on Load
Genset start outputs, and when mains is normal, close the
generating breaker.
3
Remote Start off Load
Genset start outputs, and when mains is normal, gen breaker will
not close.
4
Lamp Test
LED indicators are all light; LED backlight is light; LED is all dark.
5
S1 Genset Fault Input
Prohibit S1 genset start when S1 genset has fault (used in circular
starting).
6
S2 Genset Fault Input
Prohibit S2 genset start when S2 genset has fault (used in circular
starting).
7
Start Inhibit Input
Prohibit genset start signal output;
In auto mode, disconnect start signal output when stop delay is
over;
In manual mode, start is inactive after genset stop when it is
stopped manually if it has started;
8
Switch Trip Input
Breaker trip fault input.
9
S1 Close Inhibit
S1 close on load are prohibited; In manual mode, manual close is
prohibited; if it is closed, then it needs to open manually; In auto
mode, if it is closed then load is disconnected or S2 takes load;
10
S2 Close Inhibit
S2 close on load are prohibited; In manual mode, manual close is
prohibited; if it is closed, then it needs to open manually; In auto
mode, if it is closed then load is disconnected or S1 takes load;
11
S1 Breaker PF IN
S1 close ready signal input; waiting for S1 PF input is active before
S1 close;
12
S2 Breaker PF IN
S2 close ready signal input; waiting for S2 PF input is active before
S2 close;
13
Key S1 Close
Same as S1 close key on the panel, and it is needed to select auto
reset button.
14
Key S2 Close
Same as S2 close key on the panel, and it is needed to select auto
reset button.
15
Alarm Reset
Remove current alarm;
16
Alarm Mute
Stop audible alarm output;
17
NEL Trip Key
Control NEL unload manually; it is needed to select auto reset
button;
18
NEL Return Key
Control NEL to load again manually; it is needed to select auto reset