HAT600P Series ATS Controller User Manual Page 19 of 58
Table 16 Other Status Information
No.
Status Name
Description
1
Start Inhibit
Genset start inhibition input is active;
2
Transfer Inhibit Input
In auto mode, it is active and ATS will no longer transfer.
3
S1 Load Inhibit
S1 close inhibition input is active;
4
S2 Load Inhibit
S2 close inhibition input is active;
5
NEL 1 Trip
NEL 1 unload outputs;
6
NEL 2 Trip
NEL 2 unload outputs;
7
NEL 3 Trip
NEL 3 unload outputs;
8
Remote Gen On Load
Remote start with load input is active;
9
Remote Gen Off Load
Remote start without load input is active;
10
Mains Abnormal Gen Start
Genset starts when mains is abnormal;
11
Genset Start
Active when genset starts;
12
Auto Mode
Current status is Auto mode;
13
Manual Mode
Current status is Manual mode.
14
Local Mode
Current status is Local Mode.
7.3
MAIN MENU INTERFACE
In the main screen, press
key and it can enter the main menu interface.
Press
and
to select different parameter line
(backlight), and then press
to enter related display
screen.
NOTE 1
: Input password to enter parameter settings; default password "01234"; operator can
change the password to prevent others changing controller configurations randomly. After change
please remember clearly; If it is forgoten, please contact company personnel.
1. Configuration
2
.
History Records
3.
Black Box Records
4
.
Harmonics Analysis
5. Auto Trans./Restore
5. Auto Trans./Restore
6
.
Start/Stop Genset
7. Language
8. Module Info
9. About