HAT600P Series ATS Controller User Manual Page 25 of 58
No.
Item
Range
Default
Description
It needs to be enabled when close
control is continuous signal and
close/open time is inactive at this time;
10
Load SW Transfer
Time
(0-9999)s
1
Load switch outputs of 4 circuits are
configured by output ports; time interval
for each switch output;
11
Load SW Close Time (0-20)s
5
Output time for load switch; when it is
set 0, load switch output is continuous
output;
12
No Opening Transfer
Enabled
(0~1)
0
0: Disable
1: Enable
When it enables, the controller will
transfer from S1 to S2, and there is no
opening control output during the
transferring process.
13
Parallel Mode Set
(0~3)
0
0: Non-parallel
1: Manual auto parallel;
2: Automatic parallel;
3: Manual parallel.
14
Volt Diff. Enabled
(0~1)
0
0: Disable
1: Enable
15
Volt Diff.
(0~50)V
5
Max. voltage difference when sync. is
completed;
16
Freq Diff.
(0~0.50)Hz
0.20
Max. frequency difference when sync. is
completed;
17
Phase Diff.
(0~20) °
5
Max. phase difference when sync. is
completed;
18
Fail to Sync Action
(0~1)
0
0: Warn Alarm
1: Fault Alarm
It continues to wait for sync when sync
fails until it closes after sync;
For warning alarm, it is removed when
sync is completed or exit from sync.
For fault alarm, it needs to press alarm
reset to remove alarm.
19
Transfer in Sync Fail
(0~1)
0
0: Disable
1: Enable
After sync fails, close without sync shall
be conducted and fail to sync alarm also
isn't issued;
20
Fail to Sync Delay
(0~9999)s
120
Time for waiting for sync success; if it is
over time, then sync fails;
21
Sync. Close/Open
Detection Time
(0.1~1.0)s
0.6
At the time of sync transfer, sync
close/open output delay starts; during
this period if correct close status is
detected, then stop close/open pulse
output; if delay is over and close/open
status is not detected, then close/open
failure alarm shall be initiated;
22
ATS Power Type
(0~1)
1
0: DC Power Supply
1: AC Power Supply
23
ATS Power Low
Point
(0~200)%
70
Min. AC supply voltage for switch; if it is
lower than this value, then switch
cannot be transferred;
24
ATS Power High
(0~400)%
130
Max. AC supply voltage for switch; if it is