HAT600P Series ATS Controller User Manual Page 30 of 58
No.
Item
Range
Default
Description
Output 2 Contents
35
Combined 4 or
Output Active Type
(0~1)
0
0: Output (N/O);
1: Output (N/C)
36
Combined 4 or
Output Contents
(0~92)
0
Not Used
37
Combined 5 or
Output 1 Active Type
(0~1)
0
0: Output (N/O);
1: Output (N/C)
38
Combined 5 or
Output 1 Contents
(0~92)
0
Not Used
39
Combined 5 or
Output 2 Active Type
(0~1)
0
0: Output (N/O);
1: Output (N/C)
40
Combined 5 or
Output 2 Contents
(0~92)
0
Not Used
41
Combined 5 or
Output Active Type
(0~1)
0
0: Output (N/O);
1: Output (N/C)
42
Combined 5 or
Output Contents
(0~92)
0
Not Used
43
Combined 6 or
Output 1 Active Type
(0~1)
0
0: Output (N/O);
1: Output (N/C)
44
Combined 6 or
Output 1 Contents
(0~92)
0
Not Used
45
Combined 6 or
Output 2 Active Type
(0~1)
0
0: Output (N/O);
1: Output (N/C)
46
Combined 6 or
Output 2 Contents
(0~92)
0
Not Used
47
Combined 6 or
Output Active Type
(0~1)
0
0: Output (N/O);
1: Output (N/C)
48
Combined 6 or
Output Contents
(0~92)
0
Not Used
Module Settings
1
Power On Mode
(0~2)
0
0: Last Mode (reserved the mode before
power off)
1: Manual
2: Auto
2
Language
(0~2)
0
0: Simplified Chinese
1: English
2: Other (Users can self define module
language by PC software; default:
English.)
3
Password
(00000~65535) 01234
For entering parameter setting
4
Module Address
(1~254)
1
RS485 communication address
5
Com Baud Rate
(0~3)
2
0: 2400 bps
1: 4800 bps
2: 9600 bps
3: 19200 bps
6
Com Stop Bit
(1~2)
2
1/2 bit can be set;
7
Com Parity
(0~2)
0
0: None
1: Odd Parity
2: Even Parity
8
Communication Set
(0~3)
0
0: Enable COM Adj/Ctrl
1: Disable COM Control
2: Disable COM Adjust
3: DisableCOM Adj/Ctrl
9
Date/Time Setting
10
LCD Backlight Delay (1-3600)min
5
Enlightened time for LCD backlight;