background image

                                         

 

HAT600P Series ATS Controller User Manual                                                                              Page 34 of 58

 

No. 

Items 

Description 

42

 

 

NEL3 Trip Control 

43

 

 

Reserved 

 

44

 

 

Reserved 

 

45

 

 

S1 Closed Status 

The closed status of S1;   

46

 

 

S2 Closed Status 

The closed status of S2;   

47

 

 

S1 Genset Start 

Control S1 genset start; used for system S1-Gen S2-Gen; 

48

 

 

S2 Genset Start 

Control S2 genset start; used for system S1-Gen S2-Gen; 

49

 

 

ATS Power L1 

Power supply for ATS. 

50

 

 

ATS Power L2 

51

 

 

ATS Power L3 

52

 

 

ATS Power N   

53

 

 

Remote Control Output 

It is controlled by RS485 communication command.   

54

 

 

Input 1 Status 

Programmable input status; 

55

 

 

Input 2 Status 

56

 

 

Input 3 Status 

57

 

 

Input 4 Status 

58

 

 

Load 1 Close   

Load 1-4 close in order after S1 load supply or S2 load 
supply; After ATS open, load switch close outputs are all 
disconnected;   

59

 

 

Load 2 Close 

60

 

 

Load 3 Close 

61

 

 

Load 4 Close 

62

 

 

Reserved   

 

63

 

 

Reserved 

 

64

 

 

S1 Blackout 

S1 power status; 

65

 

 

S1 Over Volt 

66

 

 

S1 Under Volt 

67

 

 

S1 Over Freq 

68

 

 

S1 Under Freq 

69

 

 

S1 Loss Of Phase 

70

 

 

S1 Phase Seq Wrong 

71

 

 

Reserved 

 

72

 

 

Reserved 

 

73

 

 

S2 Blackout 

S2 power status;   

74

 

 

S2 Over Volt 

75

 

 

S2 Under Volt 

76

 

 

S2 Over Freq 

77

 

 

S2 Under Freq 

78

 

 

S2 Loss Of Phase 

79

 

 

S2 Phase Seq Wrong 

80

 

 

Reserved 

 

81

 

 

Reserved 

 

82

 

 

Sync Fail 

Only for HAT600PS;   

83

 

 

Sync Waiting 

Only for HAT600PS;   

84

 

 

Switching 

Output in the process of switch transfer;   

85

 

 

Battery Under Volt 

Output at battery under voltage alarm;   

86

 

 

Battery Over Volt 

Output at battery over voltage alarm; 

87

 

 

Gen Inhibit Work 

Output in continuous time for scheduled not start; 

88

 

 

Scheduler Gen Start 

Output in continuous time for scheduled start;   

89

 

 

Close Fault of Two Circuits at 
the same time   

Output when the two circuits close at the same time;   

90

 

 

Electrical Interlock Release 

When parallel mode is active, the electrical interlock release 
will output. Only for HAT600PS. 

91

 

 

Unload Output   

When S1 Mains and S2 Gen, S1 Gen and S2 Mains, unload 
outputs when mains is offload. 

92

 

 

Reserved   

 

Содержание HAT600P Series

Страница 1: ...HAT600P SERIES HAT600P HAT600PB HAT600PI HAT600PBI HAT600PS ATS CONTROLLER USER MANUAL...

Страница 2: ...ct names used within this publication is owned by their respective companies SmartGen Technology reserves the right to change the contents of this document without prior notice Table 1 Software Versio...

Страница 3: ...e 2 Symbol Illustration Symbol Illustration NOTE Implies or indicate operator to operate rightly CAUTION Indicates wrong operation may lead to impair apparatus HAZARD Indicates wrong operation may lea...

Страница 4: ...ETS 21 8 2 3 SCHEDULED GEN START 22 8 2 4 SCHEDULE NOT WORK 22 9 PARAMETER SETTINGS 23 9 1 ILLUSTRATION 23 9 2 PARAMETER CONFIGURATION LIST 23 9 3 DIGITAL INPUT PORT FUNCTION DESCRIPTION 31 9 4 DIGITA...

Страница 5: ...ATION CONFIGURATION 47 17 1 ILLUSTRATION 47 17 2 RS485 COMMUNICATION PORT 47 17 3 USB COMMUNICATION PORT 47 17 4 ETHERNET COMMUNICATION PORT 47 18 TERMINAL DESCRIPTION 48 18 1 CONTROLLER TERMINAL DESC...

Страница 6: ...etect 2 way 3 phase voltage make accurate judgment and output passive control switch for occurred abnormal voltages over under voltage loss of phase over under frequency This controller is applicable...

Страница 7: ...T600PI HAT600PBI HAT600PS DC Supply AC Supply LN90V 305V Current Monitor Synch Transfer Input Port No Fixed Flexible 2 4 2 4 2 4 2 4 2 4 Output Port No Fixed Flexible 2 6 2 6 2 6 2 6 2 6 Genset Contro...

Страница 8: ...al mode With local mode the controller only displays data parameter when it is active and the switch needs to be transferred by external operations Electrical interlock release function for switching...

Страница 9: ...Power Consumption 4W Standby mode 2W AC Voltage Input PT or PT Secondary is not used AC system HAT600P HAT600PI HAT600PB HAT600PBI HAT600PS 3P4W L L 80 625 V 80 528 V 80 520 V UL certification 3P3W L...

Страница 10: ...ensions 198mmx154mmx54mm Panel Cutout 186mm x 141mm Operating Conditions Temperature 25 70 C Humidity 20 93 RH Temperature 55 C UL certification Storage Condition Temperature 30 80 C Protection Rank F...

Страница 11: ...t Power kVA Load 3 Phase Power Facor PF Load Average Power Factor PF Voltage Difference of S1 and S2 Frequency Difference of S1 and S2 Phase Difference of S1 and S2 Continuous Power Supply Time Contin...

Страница 12: ...se phase sequence Lamp Off S2 Power none voltage S2 Close Status Indicator Lamp On S2 close auxiliary status input is active Alarm Indicator Lamp Slow Flashing flashes when warning alarm occurs 1 time...

Страница 13: ...e press to scroll up screen After entering menu page move up cursor or increase the value where the cursor is Press longer and it can mute alarms Set Confirm Key In main page press to enter menu page...

Страница 14: ...ce the difference of average value of 3 phase voltages Synchronous Frequency Difference Synchronous Phase Difference and Analogue Synchronous Meter Current page content and position alarm status indic...

Страница 15: ...us indication information and action countdown S1 Voltage Status S2 Voltage Status Switch Status Genset Status Current page content and position alarm status indication information and action countdow...

Страница 16: ...Power value is within the specified range 4 S2 Voltage None Voltage is 0 5 S2 Voltage High Voltage is above the pre set upper value 6 S2 Voltage Low Voltage is below the pre set lower value 7 S2 Frequ...

Страница 17: ...gets ready PF is active before S2 closes 16 Elevator Delay Delay time before switch transfer elevator control outputs 17 S1 On Load S1 was already closed and S1 is taking load 18 S2 On Load S2 was alr...

Страница 18: ...11 Sync Fail Fault Sync failure action is set to fault when it is over delay time fault alarms 12 S1 S2 Close At the same time It alarms when S1 close signal input and S2 close signal input are active...

Страница 19: ...starts when mains is abnormal 11 Genset Start Active when genset starts 12 Auto Mode Current status is Auto mode 13 Manual Mode Current status is Manual mode 14 Local Mode Current status is Local Mod...

Страница 20: ...et start stop menu interface is as below 1 Return 2 S1 Genset Stop 3 S1 Genset Start 4 S2 Genset Stop 5 S2 Genset Start Press Up Down key to select different parameter line backlight and press Confirm...

Страница 21: ...tification countdown is initiated Before the end of fault identification countdown if S1 generating is normal S1 takes the load as soon as it is normal After the end of S1 cycle running countdown S2 s...

Страница 22: ...time is up When scheduled start lasting time is over start signal is disconnected Scheduled Run On Load or Off Load can be set Scheduled Start On Load genset start outputs and when generating is OK g...

Страница 23: ...l to abnormal 5 Master Slave Set 0 1 0 0 S1 Master 1 S2 Master 6 System Type Set 0 3 0 0 S1 Mains S2 Gen 1 S1 Gen S2 Mains 2 S1 Mains S2 Mains 3 S1 Gen S2 Gen 7 AC System 0 3 0 0 3 Phase 4 Wire 1 3 Ph...

Страница 24: ...is the set time Enable close open pulse output time is the set close open time 2 Close Time 0 1 20 0 s 5 0 Outputted pulse time of close relay 3 Open Time 0 1 20 0 s 5 0 Outputted pulse time of open...

Страница 25: ...se Diff 0 20 5 Max phase difference when sync is completed 18 Fail to Sync Action 0 1 0 0 Warn Alarm 1 Fault Alarm It continues to wait for sync when sync fails until it closes after sync For warning...

Страница 26: ...Disable 1 Enable 8 Battery Under Volt Warn Enable 0 1 0 0 Disable 1 Enable 9 Battery Under Volt Warn 0 100 0 V 10 0 It occurs when battery voltage is lower than the set value 10 Battery Under Volt Ret...

Страница 27: ...January Bit1 February Bit2 March Bit3 April Bit4 May Bit5 June Bit6 July Bit7 August Bit8 September Bit9 October Bit10 November Bit11 December 13 Inhibit Date 1 31 1 Date of not start in every month 1...

Страница 28: ...3600 s 5 18 NEL Over Power Val 2 0 200 100 When load power is over the set value unload control outputs after delay 19 NEL Over Power Delay 2 0 3600 s 1 20 NEL Return Enable 0 1 0 0 Disable 1 Enable...

Страница 29: ...tive Type 0 1 1 0 Output N O 1 Output N C 18 Combined 1 Or Output Contents 0 92 0 Not Used 19 Combined 2 or Output 1 Active Type 0 1 0 0 Output N O 1 Output N C 20 Combined 2 or Output 1 Contents 0 92...

Страница 30: ...utput 2 Active Type 0 1 0 0 Output N O 1 Output N C 46 Combined 6 or Output 2 Contents 0 92 0 Not Used 47 Combined 6 or Output Active Type 0 1 0 0 Output N O 1 Output N C 48 Combined 6 or Output Conte...

Страница 31: ...ar starting 6 S2 Genset Fault Input Prohibit S2 genset start when S2 genset has fault used in circular starting 7 Start Inhibit Input Prohibit genset start signal output In auto mode disconnect start...

Страница 32: ...alarm occurs when it is active HVD100 voltage detection module as signal input is needed 32 Switch Output Voltage Abnormal Warn After this port is configured warning alarm occurs when it is active HV...

Страница 33: ...Control Output before load is power off or switch transfer used to control running elevator to stop at the nearest level until transfer is finished 20 Fire Control Linkage Output when forced to open...

Страница 34: ...Blackout S1 power status 65 S1 Over Volt 66 S1 Under Volt 67 S1 Over Freq 68 S1 Under Freq 69 S1 Loss Of Phase 70 S1 Phase Seq Wrong 71 Reserved 72 Reserved 73 S2 Blackout S2 power status 74 S2 Over V...

Страница 35: ...e Contents of AND condition output SW3 Input port 3 is active Close when AND condition output SW3 is active inactive close when active disconnect when inactive Output result is as below When input por...

Страница 36: ...2 power status Record date and time Press to check the detailed information of current records Action Event 010 200 Closing S2 Record type serial No total record number Record event S1 phase voltage S...

Страница 37: ...and Power of current time point Press or to exit the detailed data interface Closing S2 19 09 28 10 07 18 10s Record event Record time point S1 power status S1 phase voltage S1 frequency S1 Available...

Страница 38: ...c display of U1 A phase voltage 15 19 times harmonic display of U1 A phase voltage 21 times harmonic display of U1 A phase voltage 13 AUTO RESTORE TIME SETTING In menu page select 6 Auto Restore Time...

Страница 39: ...troller is in the auto mode Under auto mode the controller will switch automatically to ensure power supply for loading according to S1 S2 status switch priority and Auto Trans Restore status The foll...

Страница 40: ...HAT600P Series ATS Controller User Manual Page 40 of 58 14 2 2 AUTO TRANSFER NON RESTORE MUTUAL BACKUP ACTIVE Fig 7 Auto Transfer Non Restore Diagram Mutual Backup Active...

Страница 41: ...FER NON RESTORE MUTUAL BACKUP INACTIVE Fig 8 Auto Transfer Non Restore Diagram Mutual Backup Inactive NOTE Master power S1 close needs to transfer to manual mode by close operation key otherwise in au...

Страница 42: ...ly phase difference shall not be set too big Otherwise load impact will be too big at closing Fail To Sync Action Warning alarm or fault alarm can be set after sync failure it continues waiting for sy...

Страница 43: ...lse output At the same time S2 open pulse outputs until S2 open status is detected or delay is over sync close open detection time disconnect S2 open pulse outputs In synchronizing process if close op...

Страница 44: ...stopped If sync waiting is overtime sync failure warning alarm is initiated but it will continue waiting to sync until sync is completed or cancel sync close by pressing close key 14 3 4 AUTO SYNC CL...

Страница 45: ...ply 16 The upper and lower thresholds of AC supply voltage meets requirements 17 ATS supply power of output port setting is phase voltage or line voltage For example taking ATS power supply as phase v...

Страница 46: ...nnection set value after the auto reconnection delay NEL3 will be reconnected for the earliest and next is NEL2 NEL1 Fig 11 NEL Control Time Sequence 16 3 MANUAL TRIP If NEL manual trip input is activ...

Страница 47: ...PS 17 2 RS485 COMMUNICATION PORT Communication Protocol Modbus RTU Communication Parameters Module address 1 range 1 254 Baud rate 9600 bps 2400 4800 9600 19200bps Data bit 8bit Parity bit None None O...

Страница 48: ...Description Pin Items Description Notes 1 S1 close output Volt free relay N O output 250VAC 16A capacity 2 3 S2 close output Volt free relay N O output 250VAC16A capacity 4 5 Aux output 1 N C Default...

Страница 49: ...free relay N O output Default S2 open control Capacity 8A 250VAC 30 31 Aux output 5 Voltage free relay N O output Default self defined combination output 1 Capacity 8A 250VAC 32 42 Aux output 6 Volta...

Страница 50: ...ION 18 2 1 DC SUPPLY HAT600P series controller are all DC supply fitted with supply voltage range 8 35 VDC Fig 16 DC Supply 18 2 2 AC SUPPLY HAT600PB HAT600PBI HAT600PS controllers are AC supply fitte...

Страница 51: ...d Adapter connection is as below Fig 18 RS485 Connection 19 TYPICAL APPLICATION WIRING DIAGRAM Fig 19 SGQ N T Application Diagram Table 23 Related Settings Part of Parameter Settings Switch Type Setti...

Страница 52: ...User Manual Page 52 of 58 Fig 20 SGQ M Application Diagram Table 24 Related Settings Part of Parameter Settings Switch Type Setting PC two stage Aux Output 1 ATS Power L Aux Output 2 ATS Power N Aux...

Страница 53: ...ge 53 of 58 Fig 21 AtyS d Application Diagram Table 25 Related Settings Part of Parameter Settings Switch Type Setting PC three stage Aux Output 1 ATS Power L Aux Output 2 ATS Power N Aux Output 3 S1...

Страница 54: ...22 Feiteng Application Diagram Table 26 Related Settings Part of Parameter Settings Switch Type Setting CB Class CC Class Aux Output 1 ATS Power L Aux Output 2 ATS Power N Aux Output 3 S1 Open Output...

Страница 55: ...ler User Manual Page 55 of 58 Fig 23 Contactor Application Diagram Table 27 Related Settings Part of Parameter Settings Switch Type Setting CB Class CC Class Aux Output 6 Genset Start Output Close Con...

Страница 56: ...ut 3 S1 Open Output Aux Output 4 S2 Open Output Aux Output 6 Genset Start Output NOTE 1 Above are HAT600P series function application diagrams among which HAT600P HAT600PB are not current sampling inp...

Страница 57: ...g 26 Clip Installation Illustration NOTES CAUTION Risk of electric shock Please cut off the power of the controller before maintenance WARNING Risk of electric shock Do not remove the rear shell of th...

Страница 58: ...r network wires are correctly connected Programmable output error Check programmable output connections pay attention to Normally opened and closed Check the output parameters settings and output type...

Отзывы: