HAT600P Series ATS Controller User Manual Page 34 of 58
No.
Items
Description
42
NEL3 Trip Control
43
Reserved
44
Reserved
45
S1 Closed Status
The closed status of S1;
46
S2 Closed Status
The closed status of S2;
47
S1 Genset Start
Control S1 genset start; used for system S1-Gen S2-Gen;
48
S2 Genset Start
Control S2 genset start; used for system S1-Gen S2-Gen;
49
ATS Power L1
Power supply for ATS.
50
ATS Power L2
51
ATS Power L3
52
ATS Power N
53
Remote Control Output
It is controlled by RS485 communication command.
54
Input 1 Status
Programmable input status;
55
Input 2 Status
56
Input 3 Status
57
Input 4 Status
58
Load 1 Close
Load 1-4 close in order after S1 load supply or S2 load
supply; After ATS open, load switch close outputs are all
disconnected;
59
Load 2 Close
60
Load 3 Close
61
Load 4 Close
62
Reserved
63
Reserved
64
S1 Blackout
S1 power status;
65
S1 Over Volt
66
S1 Under Volt
67
S1 Over Freq
68
S1 Under Freq
69
S1 Loss Of Phase
70
S1 Phase Seq Wrong
71
Reserved
72
Reserved
73
S2 Blackout
S2 power status;
74
S2 Over Volt
75
S2 Under Volt
76
S2 Over Freq
77
S2 Under Freq
78
S2 Loss Of Phase
79
S2 Phase Seq Wrong
80
Reserved
81
Reserved
82
Sync Fail
Only for HAT600PS;
83
Sync Waiting
Only for HAT600PS;
84
Switching
Output in the process of switch transfer;
85
Battery Under Volt
Output at battery under voltage alarm;
86
Battery Over Volt
Output at battery over voltage alarm;
87
Gen Inhibit Work
Output in continuous time for scheduled not start;
88
Scheduler Gen Start
Output in continuous time for scheduled start;
89
Close Fault of Two Circuits at
the same time
Output when the two circuits close at the same time;
90
Electrical Interlock Release
When parallel mode is active, the electrical interlock release
will output. Only for HAT600PS.
91
Unload Output
When S1 Mains and S2 Gen, S1 Gen and S2 Mains, unload
outputs when mains is offload.
92
Reserved