HAT600P Series ATS Controller User Manual Page 20 of 58
8
GENSET START/STOP OPERATION
8.1
START/STOP GENSET IN MANUAL MODE
8.1.1
START/STOP GENSET ON PANEL
In main menu interface, select "6. Start/Stop Genset", and enter genset start operation manually.
When system type is "S1 Mains S2 Gen", "S1 Gen S2 Mains", "S1 Mains S2 Mains", start/stop genset
manually.
Menu interface is as below.
1. Return
2. Genset Stop
3. Genset Start
Press Up/Down key to select different parameter line
(backlight), and press Confirm key to confirm.
Genset Stop: Disconnect the outputted genset start signal, which is to control genset stop.
Genset Start: Control genset start signal output, which is to control genset start.
For system "S1 Gen S2 Gen", manual genset start/stop menu interface is as below.
1. Return
2. S1 Genset Stop
3. S1 Genset Start
4. S2 Genset Stop
5. S2 Genset Start
Press Up/Down key to select different parameter line
(backlight), and press Confirm key to confirm.
S1 Genset Stop: Disconnect the outputted S1 genset start signal, which is to control S1 genset stop.
S1 Genset Start: Control S1 genset start signal output, which is to control S1 genset start.
S2 Genset Stop: Disconnect the outputted S2 genset start signal, which is to control S2 genset stop.
S2 Genset Start: Control S2 genset start signal output, which is to control S2 genset start.
8.1.2
REMOTE START/STOP GENSET
Send remote start/stop commands by RS485 port (Modbus-RTU protocol control), ETHERNET port
(Modbus TCP/IP protocol control).
Remote Stop: Disconnect the outputted genset start signal, which is to control genset stop.
Remote Start: Control genset start signal output, which is to control genset start.