HAT600P Series ATS Controller User Manual Page 9 of 58
measuring, remote debugging functions by ModBus TCP/IP; it can remote control genset
start/stop, ATS close and open;
—
Suitable for multiple AC system types (3Ph 4W, 3Ph 3W, Single Phase 2W, 2 Ph 3W);
—
Master and backup power supply can be set; ATS can normally work if one circuit is normal;
—
Controller uses metal clips to fix;
—
Modular structure design, anti-flammable ABS shell, pluggable wire terminal, built-in installation
method; structure is compact and installation is easy.
4
SPECIFICATION
Table 4 Performance Parameters
Items
Contents
Operating Voltage
1. DC 8.0V~35.0V, continuous power supply; DC reverse connection
protection;
2. AC power A1-N1/A2-N2 supply; voltage range AC (90~305)V
(HAT600PB/HAT600PBI/HAT600PS);
1. DC 12.0V~30.0V, continuous power supply; DC reverse connection
protection (UL certification);
2. AC power A1-N1/A2-N2 supply; voltage range AC (90~300)V
(HAT600PB/HAT600PBI/HAT600PS)(UL certification);
Power Consumption <4W(Standby mode
:
<2W)
AC Voltage Input
(PT
or
PT
Secondary is not
used.)
AC system
HAT600P/HAT600PI
HAT600PB/HAT600PBI/HAT600PS
3P4W (L-L)
(80~625)V
(80~528)V
(80~520)V (UL certification)
3P3W (L-L)
(80~625)V
N/A
2P3W (A-B)
(80~625)V
(80~528)V
(80~520)V (UL certification)
1P2W (L-N)
(50~360)V
(50~305)V
(50~300)V (UL certification)
Voltage resolution: 1V; Accuracy: 1%
AC Frequency
50/60Hz
Range: 15Hz-75Hz
Resolution: 0.01Hz
Accuracy: 0.1Hz
AC Current
Rated: 5A
Range: 0A-10A
Resolution: 0.1A
Accuracy: 2%
S1 Close Relay
Output
16A AC250V Volt free output
6A AC250V
Volt free output (UL certification)
S2 Close Relay
Output
16A AC250V Volt free output
6A AC250V
Volt free output (UL certification)
Programmable
Relay Output 1-2
16A AC250V Volt free output
6A AC250V Volt free output (UL certification)
Programmable
Relay Output 3-6
8A AC250V Volt free output
6A AC250V
Volt free output (UL certification)
S1 Close Signal
Input
GND connected (B-) is active, low voltage 1.2VDC, high voltage 60VDC
S2 Close Signal
Input
Digital Input 1-4
RS485 Port
Isolated, half-duplex, 2400/4800/9600/19200 baud rate can be set,
Modbus-RTU communication protocol, farthest communication distance
1000m