User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
•
Low Limit
parameter set as
0mA
,
•
High Limit
parameter set as
20mA
,
–
Scaling
parameter set as
linear
,
–
press the
Configure scaling
button,
•
in
Output unit
parameter write
A
,
•
in
Input value
parameter in the
Point 1
section write
0mA
,
•
in
Output value
parameter in the
Point 1
section write
0A
,
•
in
Input value
parameter in the
Point 2
section write
20mA
,
•
in
Output value
parameter in the
Point 2
section write
5A
,
–
for
Display
block parameters,
•
Format
parameter set as
numeric
,
•
Precision
parameter set as
0.0
,
•
in
Graph low
parameter write
0A
,
•
in
Graph high
parameter write
5A
,
–
all the other parameters should be on default settings,
The configuration steps are shown in
b) For voltage,
–
using the arrows in the top navigation bar, select any
logical channel
such as 21,
–
in the
Name
parameter write
Voltage"
,
–
Mode
parameter set as
Hardware input
,
–
Source
parameter set as
Inp. A5: Voltage
–
press the
Source configuration
button to set the source configuration options:
•
Mode
parameter set as
0-10V
, because this voltage range comes from
the voltage converter,
•
Low Limit
parameter set as
0V
,
•
High Limit
parameter set as
10V
,
–
Scale
parameter set as
linear
,
–
press the
Configure scaling
button,
•
in
Output unit
parameter write
V
,
•
in
Input value
parameter in the
Point 1
section write
0V
,
•
in
Output value
parameter in the
Point 1
section write
0V
,
•
in
Input value
parameter in the
Point 2
section write
10V
,
•
in
Output value
parameter in the
Point 2
section write
400V
,
–
for
Displaying
block parameters,
•
Format parameter set as
numeric
,
•
Precision
parameter set as
0.0
,
•
in
Graph low
parameter write
0V
,
•
in
Graph high
parameter write
400V
,
–
all the other parameters should be on default settings,
122